Table 36: Input signals, G2.2
Index Parameter Min Max Unit Default Cust ID Description
P2.2.16 AI1 signal range 0 2 0 320
0 = 0—10 V (0—20
mA*)
1 = 2—10 V (4 – 20
mA*)
2 = Custom range*
P2.2.17
AI1 custom mini-
mum setting
–160.00 160.00 % 0.00 321
P2.2.18
AI1 custom maxi-
mum setting
–160.00 160.00 % 100.0 322
P2.2.19 AI1 inversion 0 1 0 323
0 = Not inverted
1 = Inverted
P2.2.20 AI1 filter time 0.00 10.00 s 0.10 324 0 = No filtering
P2.2.21
AI2 signal selec-
tion
0.1 E.10 A.2 388
0 = 0—20 mA (0—
10 V *)
1 = 4 – 20 mA (2—
10 V *)
2 = Custom range*
P2.2.22 AI2 signal range 0 2 1 325
0 = 0—20 mA*
1 = 4—20 mA*
2 = Customised*
P2.2.23
AI2 custom mini-
mum setting
-160.00 160.00 % 0.00 326
P2.2.24
AI2 custom maxi-
mum setting
-160.00 160.00 % 0.00 327
P2.2.25 AI2 inversion 0 1 0 328
0 = Not inverted
1 = Inverted
P2.2.26 AI2 filter time 0.00 10.00 s 0.10 329 0 = No filtering
P2.2.27
Motor potentiom-
eter ramp time
0.1 2000.0 Hz/s 10.0 331