CHAPTER 6 - DETAILED PARAMETER DESCRIPTION
110
Range
[Factory Setting]
Parameter Unit Description / Notes
P204 Action
0, 1, 2, Not used:
6, 9, 12 No action
3 Resets the parameters from P043 to P050
4 Resets the parameters from P053 to P058
5 Loads Factory Default:
LoadscurrentSoft-Starterparameters
with factory settings
7 Loads User 1:
LoadscurrentSoft-Starterparameters
with the values stored in Memory 1.
8 Loads User 2:
LoadscurrentSoft-Starterparameters
with the values stored in Memory 2.
10 Save User 1:
Transfers the current parameter
contents of the Soft-Starter to memory 1
11 Save User 2:
Transfers the current parameter
contents of the Soft-Starter to memory 2
13 ErasestheSoftPLCapplicative
14 Resets the parameters from P952 to P969
15, 16 Use reserved to the factory
NOTE!
Parameter loading/saving will be executed only after parameter
setting and after the key has been pressed .
This Parameter selects which parameter listed in table 6.23 will be
displayed after the Soft-Starter has been powered-up.
P205 0 to 9
Display Default [ 2 ]
Selection -
Table 6.22 - Action of loading/saving parameters
Table 6.23 - Options display default
In the event of a fault trip E03, E04, E05, E06, E16, E32, E65, E66,
E70, E74, E78, E79, E80 or E81, the Soft-Starter SSW-06 can initiate
an automatic reset after the time given by P206 has elapsed.
If P206 ≤ 2 Auto-Reset does not occur.
If after Auto-Reset the same fault is repeated three times consecu-
P206 0 to 600
Auto-Reset Time [ 0=Inactive ]
1s
P205 Status
0 P001 (Soft-Starter current % In of the Soft-Starter)
1 P002 (Motor current % In of the Motor)
2 P003 (Motor current (A))
3 P004(SupplyLineVoltage(V))
4 P005(SupplyLineFrequency(Hz)
5 P006 (Soft-Starter Status)
6 P007 (Output Voltage (V))
7 P008 (Power Factor)
8 P009 (Motor Torque % Tn of the Motor)
9 P010 (Output Power)

Table of Contents