CHAPTER 3 - INSTALLATION AND CONNECTION
48
Table 3.8 presents the short circuit capacity, Standard Fault, of the
power supply (symmetric Arms) at which the SSW-06 can be installed,
provided that protected by means of regular fuses or circuit breakers,
usedintheULtests.
Model
Nominal
Rating
Short Circuit
Rating
≤600V
Circuit Breaker
(CB)-UL489
any MCCB
Ultra-fast
Fuses
SSW-06.0010 10 A 5 kA < 40 A Ferraz 40 A NTD
SSW-06.0016 16 A 5 kA < 40 A Ferraz 60 A NTD
SSW-06.0023 23 A 5 kA < 40 A Ferraz 8 0 A NTD
SSW-06.0030 30 A 5 kA < 40 A Ferraz 80 A NTD
SSW-06.0045 45 A 5 kA < 150 A Ferraz 125 A NTD
SSW-06.0060 60 A 5 kA < 150 A Ferraz 125 A NTD
SSW-06.0085 85 A 10 kA < 150 A Bussmann 200 A
SSW-06.0130 130 A 10 kA < 225 A Bussmann 250 A
SSW-06.0170 170 A 10 kA < 250 A Bussmann 450 A
SSW-06.0205 205 A 10 kA < 250 A Bussmann 500 A
SSW-06.0255 255 A 18 kA < 400 A Bussmann 500 A
SSW-06.0312 312 A 18 kA < 400 A Bussmann 500 A
SSW-06.0365 365 A 18 kA < 600 A Bussmann 550 A
SSW-06.0412 412 A 18 kA < 600 A Bussmann 700 A
SSW-06.0480 480 A 30 kA < 600 A Bussmann 900 A
SSW-06.0604 604 A 42 kA < 800 A Bussmann 900 A
SSW-06.0670 670 A 42 kA < 1200 A Bussmann 900 A
SSW-06.0820 820 A 42 kA < 1200 A Bussmann 1400 A
SSW-06.0950 950 A 42 kA < 1200 A Bussmann 1600 A
SSW-06.1100 1100 A 85kA≤480V < 1600 A Bussmann 1600 A
SSW-06.1400 1400 A 85kA≤480V < 2000 A Bussmann 2000 A
Table 3.8 - Short circuit capacity standard connection - UL Standard Fault
Thefusesintable3.8usedintheSSW-06ULtestsareoftheultra-
fast (aR) type, which also reduce the risk of SCRs being burned by
over current transients.