CHAPTER 6 - DETAILED PARAMETER DESCRIPTION
119
DenestheSoft-StarterSSW-06addressontheserialModbus-RTU
communication network.
For more information, refer to the Serial Communication Manual
for the Soft-Starter SSW-06.
P308
(1)(2)
1 to 247
Soft-Starter Address [ 1 ]
on the Serial 1
Communication
Network
P309
(1)(2)
0 to 9
Fieldbus [ 0=Inactive ]
Communication -
Board Enabling
Table 6.34 - Fieldbus Communication Protocol Type
Range
[Factory Setting]
Parameter Unit Description / Notes
EnablesanddenestheprotocoltypeoftheFieldbusCommunica-
tion Board.
For more information, refer to the Fieldbus Communication Manual
for the Soft-Starter SSW-06.
NOTE!
Without a Fieldbus Communication Board, this parameter
must remain at 0 (not used).
ATTENTION!
Always program this parameter with a voltage that exactly
matches the voltage of the model of your Soft-Starter SSW-06.
P296
(1)(2)
0 to 1
Nominal Voltage [ According to the
nominal voltage of
the Soft-Starter
SSW-06 ]
-
Table 6.33 - Voltage range
P310 0 to 1
ProbusDPorDP-V1 [0=Inactive]
Master Stop Detection 1
Table 6.35 - Selection of the Probus DP master stop detection
6.4-SERIALCOMMUNICATIONPARAMETERS-P300toP399
It allows, through the bit 6 of the control word, detecting that the
masteroftheProbusDPorDPV1isstopped.RefertotheFieldbus
communication manual for more details.
When it occurs it will indicate E29. In order to prevent the error, the
master must keep the bit 6 in 1.
ATTENTION!
Always program this parameter with a current that exactly
matches the current of the model of your Soft-Starter SSW-
06, described in the nameplate of the SSW-06. An error in
programming this parameter may damage your Soft-Starter
SSW-06.
P296 Voltage Range
0 220/575V
1 575/690V
P310 Description
0 Inactive
1 Active
P309 Action
0 Inactive
1 Probus-DP(1Inputand1Output)
2 Probus-DP(4Inputsand4Outputs)
3 Probus-DP(7Inputsand7Outputs)
4 DeviceNet (1 Input and 1 Output)
5 DeviceNet (4 Inputs and 4 Outputs)
6 DeviceNet (7 Inputs and 7 Outputs)
7 EtherNet (1 Input and 1 Output)
8 EtherNet (4 Input and 4 Output)
9 EtherNet (7 Input and 7 Output)

Table of Contents