CHAPTER 6 - DETAILED PARAMETER DESCRIPTION
117
Range
[Factory Setting]
Parameter Unit Description / Notess
DIx Parameter P263 P264 P265 P266 P267 P268
Function
(DI1) (DI2) (DI3) (DI4) (DI5) (DI6)
Not Used 0 0 0 0 0 0
Start/Stop 1 3 3 - - -
Start (Three wires) 2 4 4 - - -
Stop (Three wires) 3 1 5 - - -
General Enabling 4 5 1 - - -
FWD/REV - - - 1 1 1
Local/Remote - - - 2 2 2
No External Fault - - - 3 3 3
JOG - - - 4 4 4
BrakeO󰀨 - - - 5 5 5
Reset 5 2 2 6 6 6
Motor Thermistor - - - - - 7
Emergency Start - - 6 - - -
Table 6.30 - Functions of the Digital Inputs
the digital input is open, for extra safety, monitor real motor standstill
and disable the braking immediately. If more than one digital input
is programmed for this function, any one which is opened disables
the braking immediately.
“Emergency Start” = It makes possible start and stop the motor
during any error action, not respecting the protections of Soft-Starter
SSW-06 or the motor. This option is used for the hydraulical pumps
ofprotectionagainstre.
P277
(1)
0 to 12
RL1RelayOutput [1=Running]
Function -
P278
(1)
0 to 12
RL2RelayOutput [2=Full
Function Voltage ]
-
P279
(1)
0 to 12
RL3RelayOutput [6=NoFault]
Function -
Check the available options in table 6.31.
The status of the digital outputs can be monitored in Parameter P013.
The digital output will be enabled when the function which has been
programmed for the digital output is true.
“Not Used” = the digital outputs are disabled.
“Running” = the output will be enabled instantly with the Soft-Starter
SSW-06 Enable command, and will only be disabled when the
Soft-Starter SSW-06 receives the command Disable, or when the
end of the deceleration ramp is reached, if programmed.
“Full Voltage” = the output will be enabled when the Soft-Starter
SSW-06 reaches 100% Un and it will be disabled when the Soft-S-
tarter SSW-06 receives the command Disable.
“External By-pass” = its operation is similar to the “Full Voltage”
operation, but it must be applied only when the use of an external
By-pass contactor is required. See P140 and the recommended
setup at items 3.3 and 3.3.12.
“FWD/REV-K1” = this operation is similar to the “Running”, but it
NOTE!
The options of the digital inputs DI1, DI2 and DI3 had been mo-
diedinrelationthepreviousversionsofsoftwaretotheV1.60.
Figure 6.17 - Status of the relay digital outputs when disabled
18
19
20 21
22
23 24
RL3
RL2
RL1
X1C
NOTE!
The Emergency Start only must be used in emergency case,
otherwise the Soft-Starter SSW-06 or the motor may be da-
maged.