CHAPTER 2 - GENERAL INFORMATION
25
Programmable protections against line undervoltage and
overvoltage, and line phase imbalance;
Programmable protections against motor undercurrent and over-
current, and current imbalance between phases of the motor;
Thermal class may be programmed up to Class 45 for large motors.
The thermal memory is saved on EEPROM in case of an electronic
supply fault.
Special functions such as:
Display of the number of hours, running time, supply voltage phase,
motor current per phase, motor current in amperes, motor current
as a % of the Soft-Starter SSW-06 nominal current and the nominal
current as a % of the motor current, status of the digital inputs and
outputs;
Setting sequence after reset to factory default;
Veryexible selectionof start/stop control type,enabling the
followingselections:VoltageRamp,ConstantCurrentLimitingor
byRamp,PumpControlandConstant,LinearorQuadraticTorque
Control;
TotallyexibleTorqueControlprovidingveryhighperformance
for the most demanding applications;
Possibility of using all digital inputs, digital outputs and analog
outputsasremotePLCviaSerialandFieldbuscommunication;
Possibility of line voltage measurements monitoring by a supervi-
sory implemented through Serial or Fieldbus communication;
Monitoring and programming via software SuperDrive G2.
Indication of starting and full voltage diagnostics, and faults.
Control Hardware:
Keypad, referred to as the Human Machine Interface (HMI) with
Liquid-CrystalDisplay and easy programming.Fault conditions
can be displayed in several languages.
32Bit Microprocessor calculates the True rms voltage and current;
Measurement of the voltage and current in the three phases;
Isolated digital input for the motor PTC;
Fieldbus boards and RS-485 as options.
Power Hardware:
Compact size;
Power supply input and output connections:
Models from 10A to 820A - Input from the top and output at the
bottom of the SSW-06, with built-in By-pass contactor;
Models from 950A to 1400A - Input and output from the bottom,
without built-in By-pass contactor;
Easy assembly and maintenance;
Measurements of heatsink temperature in models 255A to 820A
through two thermostats:One thermostat to switch-on the internal
fans and the other to monitor over-heating;
Soft-Starter SSW-06 can be coupled to the motor by a standard
connection or an inside delta motor connection without requiring
optional devices.
Built-in By-pass contactor makes the Soft-Starter SSW- 06 (Mo-
dels from 10A to 820A):
More resistant to supply line oscillations after starting;
Save energy that would be dissipated through the thyristors after
the start, thus reducing the number of fans required for control
panel cooling.

Table of Contents

Other manuals for WEG SSW-06

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the WEG SSW-06 and is the answer not in the manual?

WEG SSW-06 Specifications

General IconGeneral
BrandWEG
ModelSSW-06
CategoryController
LanguageEnglish

Related product manuals