CHAPTER 3 - INSTALLATION AND CONNECTION
34
Use the minimum recommended panel dimensions and its cooling
requirements:
NOTE!
The fans recommended in table 3.3 are base on:
- a working cycle of 10 starts per hour with 3 x In of the SSW-06 for
30s at an ambient temperature of 55°C (131°F) for the models from
10A to 820A;
- a working cycle of 5 starts per hour with 30s at an ambient tempe-
rature of 40°C (104°F) for the models from 950A to 1400A.
Table 3.3 - Panel Dimensions and Cooling Requirements
Model
Panel Dimensions
Cooling
m
3
/min (CFM)
Width W
mm (in)
Heigth H
mm (in)
Depth D
mm (in)
220-575V 575-690V
SSW06.0010 -
600
(23.62)
800
(31.49)
300
(11.81)
-
SSW06.0016 -
SSW06.0023 -
SSW06.0030 -
SSW06.0045 SSW06.0045
600
(23.62)
1,000
(39.37)
400
(15.75)
-
SSW06.0060 SSW06.0060
SSW06.0085 SSW06.0085
SSW06.0130 -
SSW06.0170 SSW06.0130
600
(23.62)
1,200
(47.24)
400
(15.75)
-
SSW06.0205 SSW06.0170
- SSW06.0205
600
(23.62)
1,600
(63.00)
600
(23.62)
-
SSW06.0255 SSW06.0255
SSW06.0312 SSW06.0312
600
(23.62)
2,000
(78.74)
600
(23.62)
-
SSW06.0365 SSW06.0365
SSW06.0412 SSW06.0412
600
(23.62)
2,000
(78.74)
600
(23.62)
-
SSW06.0480 SSW06.0480
SSW06.0604 SSW06.0604
SSW06.0670 SSW06.0670
800
(31.5)
2,000
(78.74)
600
(23.62)
-
SSW06.0820 SSW06.0820
SSW06.0950 SSW06.0950
800
(31.5)
2,000
(78.74)
600
(23.62)
49.8
(1,757.30)
SSW06.1100 SSW06.1100
800
(31.5)
2,000
(78.74)
600
(23.62)
49.8 (1,757.30)
SSW06.1400 SSW06.1400 75.0 (2,648.44)