No. Name Setting Range Default
o3-02 Copy Allowed Selection 0, 1 0
Setting 0: Disabled
Setting 1: Enabled
u
o4: Maintenance Monitor Settings
n
o4-01: Cumulative Operation Time Setting
Sets the cumulative operation time of the drive. The user can also manually set this parameter to begin keeping track of
operation time from some desired value. Total operation time can be viewed in monitor U4-01.
Note: The value in o4-01 is set in 10 h units. For example, a setting of 30 will set the cumulative operation time counter to 300 h. 300 h will also
be displayed in monitor U4-01.
No. Name Setting Range Default
o4-01 Cumulative Operation Time Setting 0 to 9999 0
n
o4-02: Cumulative Operation Time Selection
Selects the conditions for how the drive keeps track of its total operation time. This time log can be viewed in monitor U4-01.
No. Name Setting Range Default
o4-02 Cumulative Operation Time Selection 0, 1 0
Setting 0: Power On Time
The drive logs the time it is connected to a power supply, regardless of whether the motor is running.
Setting 1: Run Time
The drive logs the time that the output is active including when the Run command is active (even if the motor is not rotating)
and when there is voltage output.
n
o4-03: Cooling Fan Operation Time Setting
Sets the value for how long the cooling fan has been operating. This value can be viewed in monitor U4-03. Parameter o4-03
also sets the base value used for the cooling fan maintenance, which is displayed in U4-04. Reset this parameter to 0 after
replacing the cooling fan.
Note: 1. The value in o4-03 increases after every 10 hours of use. A setting of 30 will set the cooling fan operation time counter to 300 h. “300”
will be displayed in monitor U4-03.
2. The cooling fan may require maintenance at an earlier date in harsher environments.
No. Name Setting Range Default
o4-03 Cooling Fan Operation Time Setting 0 to 9999 0
n
o4-05: Capacitor Maintenance Setting
Sets value of the maintenance monitor for the DC bus capacitors displayed in U4-05 as a percentage of the total expected
performance life. Reset this value to 0 after replacing the DC bus capacitors.
Note: The actual maintenance time will depend on the environment where the drive is used.
No. Name Setting Range Default
o4-05 Capacitor Maintenance Setting 0 to 150% 0%
n
o4-07: DC Bus Pre-Charge Relay Maintenance Setting
Sets the value of the softcharge bypass relay maintenance time displayed in U4-06 as a percentage of the total expected
performance life. Reset this value to 0 after replacing the bypass relay.
Note: The actual maintenance time will depend on the environment where the drive is used.
No. Name Setting Range Default
o4-07 DC Bus Pre-charge Relay Maintenance Setting 0 to 150% 0%
1.10 o: Operator Related Settings
YASKAWA ELECTRIC SIEP YEAHHP 01B YASKAWA AC Drive – A1000 HHP Programming Manual
165
1
Parameter Details

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the YASKAWA A1000 HHP and is the answer not in the manual?

YASKAWA A1000 HHP Specifications

General IconGeneral
SeriesA1000
Overload Capacity150% for 60 seconds
Horsepower0.5-1000 HP
Control MethodV/f Control
Protection FunctionsOvercurrent, Overvoltage, Undervoltage, Overheating, Ground Fault
CommunicationModbus, DeviceNet, Profibus, Ethernet/IP
Input Voltage200-240 V, 380-480 V
Output Voltage0-Input Voltage
Frequency400 Hz
Power Range0.4-630 kW
Operating Temperature-10°C to 50°C
Storage Temperature-20°C to 60°C
Humidity5% to 95% RH (non-condensing)
Enclosure RatingIP20, IP00
Voltage200-480 V