B.1 MEMOBUS/Modbus Configuration
Drives can be controlled from a PLC or other master device via serial communications using the MEMOBUS/Modbus protocol.
MEMOBUS/Modbus communications can be configured using one master (PLC) and up to 31 slaves. The drive has slave
functionality only, and serial communication is normally initiated from the master and responded to by the slaves.
The master performs serial communications with only one slave at a time. The address or node for each slave must be set
beforehand so that the master can communicate with the slave at that address. A slave that receives a command from the master
will perform the specified function and then send a response back to the master.
MasterPLC or other
Slave (Drive)
Figure B.1 Connecting Multiple Drives to a PLC
B.1 MEMOBUS/Modbus Configuration
314
YASKAWA ELECTRIC SIEP YEAHHP 01B YASKAWA AC Drive – A1000 HHP Programming Manual

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the YASKAWA A1000 HHP and is the answer not in the manual?

YASKAWA A1000 HHP Specifications

General IconGeneral
SeriesA1000
Overload Capacity150% for 60 seconds
Horsepower0.5-1000 HP
Control MethodV/f Control
Protection FunctionsOvercurrent, Overvoltage, Undervoltage, Overheating, Ground Fault
CommunicationModbus, DeviceNet, Profibus, Ethernet/IP
Input Voltage200-240 V, 380-480 V
Output Voltage0-Input Voltage
Frequency400 Hz
Power Range0.4-630 kW
Operating Temperature-10°C to 50°C
Storage Temperature-20°C to 60°C
Humidity5% to 95% RH (non-condensing)
Enclosure RatingIP20, IP00
Voltage200-480 V

Related product manuals