EasyManua.ls Logo

YASKAWA A1000 HHP - A.3 A: Initialization Parameters

YASKAWA A1000 HHP
360 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
A.3 A: Initialization Parameters
The A parameter group creates the operating environment for the drive. This includes the parameter Access Level, Motor
Control Method, Password, User Parameters and more.
u
A1: Initialization
No.
(Addr.
Hex)
Name Description Values Page
A1-00
(100)
<1>
Language Selection
All Modes
0: English
1: Japanese
Default: 0
Range: 0, 1
10
A1-01
(101)
<2>
Access Level Selection
All Modes
0: View and set A1-01 and A1-04. Uo-oo parameters can also be viewed.
1: User Parameters (access to a set of parameters selected by the user, A2-01
to A2-32)
2: Advanced Access (access to view and set all parameters)
Default: 2
Range: 0 to 2
10
A1-02
(102)
<1>
Control Method Selection
All Modes
0: V/f Control
1: V/f Control with PG
2: Open Loop Vector Control
3: Closed Loop Vector Control
Default: 2
Range: 0 to 3
10
A1-03
(103)
Initialize Parameters
All Modes
0: No initialization
1110: User Initialize (parameter values must be stored using parameter o2-03)
2220: 2-Wire initialization
3330: 3-Wire initialization
5550: oPE04 error reset
Default: 0
Range: 0 to 3330;
5550
11
A1-04
(104)
Password
All Modes
When the value set into A1-04 does not match the value set into A1-05,
parameters A1-01 through A1-03, A1-06, and A2-01 through A2-33 cannot
be changed.
Default: 0000
Min.: 0000
Max.: 9999
11
A1-05
(105)
Password Setting
All Modes
When the value set into A1-04 does not match the value set into A1-05,
parameters A1-01 through A1-03, A1-06, and A2-01 through A2-33 cannot
be changed.
Default: 0000
Min.: 0000
Max.: 9999
11
A1-06
(127)
Application Preset
All Modes
0: General-purpose
1: Water supply pump
2: Conveyor
3: Exhaust fan
4: HVAC fan
5: Air compressor
6:
7:
Default: 0
Range: 0 to 7
14
A1-07
(128)
DriveWorksEZ Function
Selection
All Modes
0: DWEZ Disabled
1: DWEZ Enabled
2: Digital input (enabled when H1-oo = 9F)
Default: 0
Range: 0 to 2
16
<1> Parameter setting value is not reset to the default value when the drive is initialized.
<2> Default setting value is dependent on the Application Preset selected with parameter A1-06.
A.3 A: Initialization Parameters
238
YASKAWA ELECTRIC SIEP YEAHHP 01B YASKAWA AC Drive – A1000 HHP Programming Manual

Table of Contents

Related product manuals