EasyManua.ls Logo

YASKAWA A1000 HHP - Q: Driveworksez Parameters; R: Driveworksez Connection Parameters

YASKAWA A1000 HHP
360 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
n
o4-09: IGBT Maintenance Setting
Sets the value of the IGBT maintenance time displayed in U4-07 as a percentage of the total expected performance life. Reset
this value to 0 after replacing the IGBTs.
Note: The actual maintenance time will depend on the environment where the drive is used.
No. Name Setting Range Default
o4-09 IGBT Maintenance Setting 0 to 150% 0%
n
o4-11: U2, U3 Initialization
Resets the fault trace and fault history monitors (U2-oo and U3-oo).
Note: Initializing the drive using A1-03 does not reset these monitors.
No. Name Setting Range Default
o4-11 U2, U3 Initialization 0, 1 0
Setting 0: No Action
The drive keeps the previously saved record concerning fault trace and fault history.
Setting 1: Reset Fault Data
Resets the data for the U2-oo and U3-oo monitors. Setting o4-11 to 1 and pressing the ENTER key erases fault data and
returns the display to 0.
n
o4-12: kWh Monitor Initialization
Manually resets kWh monitors U4-10 and U4-11. Initializing the drive or cycling the power will not reset these monitors.
No. Name Setting Range Default
o4-12 kWh Monitor Initialization 0, 1 0
Setting 0: No Action
The kWh data are maintained.
Setting 1: Reset kWh Data
Resets the kWh counter. The monitors U4-10 and U4-11 will display “0” after they are initialized. Setting o4-12 to 1 and
pressing the ENTER erases kWh data and returns the display to 0.
n
o4-13: Number of Run Commands Counter Initialization
Resets the Run command counter displayed in U4-02. Initializing the drive or cycling the power does not reset this monitor.
No. Name Setting Range Default
o4-13 Number of Run Commands Counter Initialization 0, 1 0
Setting 0: No Action
The Run command data are kept.
Setting 1: Number of Run Commands Counter
Resets the Run command counter. The monitor U4-02 will show 0. Setting o4-13 to 1 and pressing the ENTER key erases the
counter value and returns the display to 0.
u
q: DriveWorksEZ Parameters
These parameters are reserved for use with DriveWorksEZ. Refer to the DriveWorksEZ manual for more information.
n
q1-01 to q6-07: Reserved for Use by DriveWorksEZ
These parameters are reserved for use with DriveWorksEZ. Refer to the DriveWorksEZ manual for more information.
u
r: DriveWorksEZ Connection Parameters
These parameters are reserved for use with DriveWorksEZ. Refer to the DriveWorksEZ manual for more information.
1.10 o: Operator Related Settings
166
YASKAWA ELECTRIC SIEP YEAHHP 01B YASKAWA AC Drive – A1000 HHP Programming Manual

Table of Contents

Related product manuals