o4-09: IGBT Maintenance Setting
Sets the value of the IGBT maintenance time displayed in U4-07 as a percentage of the total expected performance life. Reset
this value to 0 after replacing the IGBTs.
Note: The actual maintenance time will depend on the environment where the drive is used.
No. Name Setting Range Default
o4-09 IGBT Maintenance Setting 0 to 150% 0%
n
o4-11: U2, U3 Initialization
Resets the fault trace and fault history monitors (U2-oo and U3-oo).
Note: Initializing the drive using A1-03 does not reset these monitors.
No. Name Setting Range Default
o4-11 U2, U3 Initialization 0, 1 0
Setting 0: No Action
The drive keeps the previously saved record concerning fault trace and fault history.
Setting 1: Reset Fault Data
Resets the data for the U2-oo and U3-oo monitors. Setting o4-11 to 1 and pressing the ENTER key erases fault data and
returns the display to 0.
n
o4-12: kWh Monitor Initialization
Manually resets kWh monitors U4-10 and U4-11. Initializing the drive or cycling the power will not reset these monitors.
No. Name Setting Range Default
o4-12 kWh Monitor Initialization 0, 1 0
Setting 0: No Action
The kWh data are maintained.
Setting 1: Reset kWh Data
Resets the kWh counter. The monitors U4-10 and U4-11 will display “0” after they are initialized. Setting o4-12 to 1 and
pressing the ENTER erases kWh data and returns the display to 0.
n
o4-13: Number of Run Commands Counter Initialization
Resets the Run command counter displayed in U4-02. Initializing the drive or cycling the power does not reset this monitor.
No. Name Setting Range Default
o4-13 Number of Run Commands Counter Initialization 0, 1 0
Setting 0: No Action
The Run command data are kept.
Setting 1: Number of Run Commands Counter
Resets the Run command counter. The monitor U4-02 will show 0. Setting o4-13 to 1 and pressing the ENTER key erases the
counter value and returns the display to 0.
u
q: DriveWorksEZ Parameters
These parameters are reserved for use with DriveWorksEZ. Refer to the DriveWorksEZ manual for more information.
n
q1-01 to q6-07: Reserved for Use by DriveWorksEZ
These parameters are reserved for use with DriveWorksEZ. Refer to the DriveWorksEZ manual for more information.
u
r: DriveWorksEZ Connection Parameters
These parameters are reserved for use with DriveWorksEZ. Refer to the DriveWorksEZ manual for more information.
1.10 o: Operator Related Settings
166
YASKAWA ELECTRIC SIEP YEAHHP 01B YASKAWA AC Drive – A1000 HHP Programming Manual