Output
frequency
Time
Zero Speed
Control
b2-04
E1-09 Min. Frequency
b2-01 Zero Speed Level
Figure 1.13 Zero Speed Control at Stop in CLV and CLV/PM
Note: If b2-01 is set lower than the minimum frequency (E1-09), then Zero Speed Control begins at the frequency set to E1-09.
n
b2-02: DC Injection Braking Current
Sets the DC Injection Braking current as a percentage of the drive rated current. The carrier frequency is automatically reduced
to 1 kHz when this parameter is set to more than 50%.
No. Name Setting Range Default
b2-02 DC Injection Braking Current 0 to 100% 50%
The level of DC Injection Braking current affects the strength of the magnetic field attempting to lock the motor shaft.
Increasing the current level will increase the amount of heat generated by the motor windings. Do not set this parameter higher
than the level necessary to hold the motor shaft.
n
b2-03: DC Injection Braking Time at Start
Sets the time of DC Injection Braking (Zero Speed Control in CLV and CLV/PM) at start. Used to stop a coasting motor before
restarting it or to apply braking torque at start. Disabled when set to 0.00 s.
No. Name Setting Range Default
b2-03 DC Injection Braking Time at Start 0.00 to 10.00 s 0.00 s
Note: Before starting an uncontrolled rotating motor (e.g., a fan motor driven by windmill effect), use DC Injection or Speed Search to stop the
motor or detect motor speed before starting it. Otherwise, motor stalling and other faults can occur.
n
b2-04: DC Injection Braking Time at Stop
Sets the time of DC Injection Braking (Zero Speed Control in CLV and CLV/PM) at stop. Used to completely stop a motor
with high inertia load after ramp down. Increase the value if the motor still coasts by inertia after it should have stopped.
Disabled when set to 0.00 s.
No. Name Setting Range Default
b2-04 DC Injection Braking Time at Stop 0.00 to 10.00 s
Determined by
A1-02
1.2 b: Application
26
YASKAWA ELECTRIC SIEP YEAHHP 01B YASKAWA AC Drive – A1000 HHP Programming Manual

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the YASKAWA A1000 HHP and is the answer not in the manual?

YASKAWA A1000 HHP Specifications

General IconGeneral
SeriesA1000
Overload Capacity150% for 60 seconds
Horsepower0.5-1000 HP
Control MethodV/f Control
Protection FunctionsOvercurrent, Overvoltage, Undervoltage, Overheating, Ground Fault
CommunicationModbus, DeviceNet, Profibus, Ethernet/IP
Input Voltage200-240 V, 380-480 V
Output Voltage0-Input Voltage
Frequency400 Hz
Power Range0.4-630 kW
Operating Temperature-10°C to 50°C
Storage Temperature-20°C to 60°C
Humidity5% to 95% RH (non-condensing)
Enclosure RatingIP20, IP00
Voltage200-480 V

Related product manuals