EasyManua.ls Logo

YASKAWA U1000 Series - Page 232

YASKAWA U1000 Series
638 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
5.4 d: Reference Settings
232 YASKAWA ELECTRIC SIEP C710636 02B YASKAWA U1000 Technical Manual
Multi-Step Speed 2
When setting terminal A3’s analog input to Multi-Step Speed 2, set H3-06 (Terminal A3 Function Selection) to 2
(Auxiliary frequency reference 1). When setting d1-02 (Frequency Reference 2) to Multi-Step Speed 2, set H3-06 to F
(Through mode).
Multi-Step Speed 3
When setting terminal A2’s analog input to Multi-Step Speed 3, set H3-10 (Terminal A2 Function Selection) to 3
(Auxiliary frequency reference 2).
When inputting 0 to 10 V to terminal A2's analog input, set H3-09 to 0, and DIP switch S1 on the control circuit
terminal board to V (voltage).
The different speed references can be selected as shown in Table 5.1 8. Figure 5.42 illustrates the multi-step speed
selection.
Table 5.18 Multi-Step Speed Reference and Terminal Switch Combinations
Figure 5. 42
Figure 5.42 Preset Reference Timing Diagram
Reference
<1> The Jog frequency overrides whatever frequency reference is being used.
Multi-Step
Speed Reference 1
H1- = 3
Multi-Step
Speed Reference 2
H1- = 4
Multi-Step
Speed Reference 3
H1- = 5
Multi-Step
Speed Reference 4
H1- = 32
Jog Reference
Selection
H1- = 6
Frequency Reference 1 (set in b1-01) OFF OFF OFF OFF OFF
Frequency Reference 2 (d1-02 or input terminal A1, A2, A3) ON OFF OFF OFF OFF
Frequency Reference 3 (d1-03 or input terminal A1, A2, A3) OFF ON OFF OFF OFF
Frequency Reference 4 (d1-04) ON ON OFF OFF OFF
Frequency Reference 5 (d1-05) OFF OFF ON OFF OFF
Frequency Reference 6 (d1-06) ON OFF ON OFF OFF
Frequency Reference 7 (d1-07) OFF ON ON OFF OFF
Frequency Reference 8 (d1-08) ON ON ON OFF OFF
Frequency Reference 9 (d1-09) OFF OFF OFF ON OFF
Frequency Reference 10 (d1-10) ON OFF OFF ON OFF
Frequency Reference 11 (d1-11) OFF ON OFF ON OFF
Frequency Reference 12 (d1-12) ON ON OFF ON OFF
Frequency Reference 13 (d1-13) OFF OFF ON ON OFF
Frequency Reference 14 (d1-14) ON OFF ON ON OFF
Frequency Reference 15 (d1-15) OFF ON ON ON OFF
Frequency Reference 16 (d1-16) ON ON ON ON OFF
Jog Frequency Reference (d1-17)
<1>
−−−ON
Time
Frequency
reference
FWD (REV) Run/Stop
d1-01
(A1)
d1-02
(A2)
d1-04
d1-05
d1-06
d1-07
d1-17
d1-09
d1-08
d1-14
d1-15
d1-16
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
d1-03
(A3)
Multi-step Speed Ref. 2
Multi-step Speed Ref. 3
Jog Reference Selection
Multi-step Speed Ref. 1
Multi-step Speed Ref. 4
SIEP_C710636_02B_1_0.book 232 ージ 015年11月25日 水曜日 午後4時56