B.3 Parameter Table
YASKAWA ELECTRIC
SIEP C710636 02B YASKAWA U1000 Technical Manual 487
Parameter List
B
E5: PM Motor Settings
E4-05
(325H)
Motor 2 Line-to-Line Resistance
Sets the phase-to-phase resistance for motor 2. Automatically set during Auto-Tuning.
Default:
<9>
Min: 0.000 Ω
Max: 65.000 Ω
253
E4-06
(326H)
Motor 2 Leakage Inductance
Sets the voltage drop for motor 2 due to motor leakage inductance as a percentage of rated
voltage. Automatically set during Auto-Tuning.
Default:
<9>
Min: 0.0%
Max: 40.0%
253
E4-07
(343H)
Motor 2 Motor Iron-Core
Saturation Coefficient 1
Set to the motor iron saturation coefficient at 50% of magnetic flux for motor 2. Automatically
set during Auto-Tuning.
Default: 0.50
Min: 0.00
Max: 0.50
253
E4-08
(344H)
Motor 2 Motor Iron-Core
Saturation Coefficient 2
Set to the motor iron saturation coefficient at 75% of magnetic flux for motor 2. This value is
automatically set during Auto-Tuning.
Default: 0.75
Min: E4-07
Max: 0.75
254
E4-09
(33FH)
Motor 2 Mechanical Loss
There is normally no need to change this parameter from the default value.
Sets the motor mechanical loss for motor 2 as a percentage of motor rated power (kW).
Default: 0.0%
Min: 0.0%
Max: 10.0%
254
E4-10
(340H)
Motor 2 Iron Loss
Sets the motor iron loss.
Default:
<9>
Min: 0 W
Max: 65535 W
254
E4-11
(327H)
Motor 2 Rated Power
Sets the motor rated capacity in kW. Automatically set during Auto-Tuning.
Default:
<9>
Min: 0.00 kW
Max: 650.00 kW
254
<9> Default setting value is dependent on the drive model (o2-04) and the Drive Duty (C6-01).
<72> Display is in the following units.
CIMR-U20028, 20042, and 40011 to 40027: 0.01 A units
CIMR-U20054 to 20248, and 40034 to 40930: 0.1 A units
No.(Addr.) Name Description Setting Page
E5-01
(329H)
<3>
Motor Code Selection
(for PM Motors)
Enter the Yaskawa motor code for the PM motor being used. Various motor parameters are
automatically set based on the value of this parameter. Setting that were changed manually will
be overwritten by the defaults of the selected motor code.
Note1. Set to FFFF when using a non-Yaskawa PM motor or a special motor.
2. If an alarm or hunting occurs even though a motor code is used, enter the value indicated
on the nameplate. For more details, refer to Auto-Tuning for Permanent Magnet
Motors on page 155.
Default:
<4>
Min: 0000
Max: FFFF
<28>
254
E5-02
(32AH)
<3>
Motor Rated Power
(for PM Motors)
Sets the rated capacity of the motor.
Default:
<14>
Min: 0.10 kW
Max: 650.00 kW
255
E5-03
(32BH)
<3>
Motor Rated Current
(for PM Motors)
Sets the motor rated current.
Default:
<14>
Min: 10% of drive rated
current
Max: 150% of drive
rated current
<72>
255
E5-04
(32CH)
<3>
Number of Motor Poles
(for PM Motors)
Sets the number of motor poles.
Default:
<14>
Min: 2
Max: 48
255
E5-05
(32DH)
<3>
Motor Stator Resistance (r1)
(for PM Motors)
Set the resistance for each motor phase.
Default:
<14>
Min: 0.000 Ω
Max: 65.000 Ω
255
E5-06
(32EH)
<3>
Motor d-Axis Inductance (Ld)
(for PM Motors)
Sets the d-axis inductance for the PM motor.
Default:
<14>
Min: 0.00 mH
Max: 300.00 mH
256
No.(Addr.) Name Description Setting Page
OLV/PM AOLV/PM
CLV
V/f w/PG
CLV/PM
V/f OLV
OLV/PM AOLV/PM
CLV
V/f w/PG
CLV/PM
V/f OLV
OLV/PM AOLV/PM
CLV
V/f w/PG
CLV/PM
V/f OLV
OLV/PM AOLV/PM
CLV
V/f w/PG
CLV/PM
V/f OLV
OLV/PM AOLV/PM
CLV
V/f w/PG
CLV/PM
V/f OLV
OLV/PM AOLV/PM
CLV
V/f w/PG
CLV/PM
V/f OLV
OLV/PM AOLV/PM
CLV
V/f w/PG
CLV/PM
V/f OLV
OLV/PM AOLV/PM
CLV
V/f w/PG
CLV/PM
V/f OLV
OLV/PM AOLV/PM
CLV
V/f w/PG
CLV/PM
V/f OLV
OLV/PM AOLV/PM
CLV
V/f w/PG
CLV/PM
V/f OLV
OLV/PM AOLV/PM
CLV
V/f w/PG
CLV/PM
V/f OLV
OLV/PM AOLV/PM
CLV
V/f w/PG
CLV/PM
V/f OLV
OLV/PM AOLV/PM
CLV
V/f w/PG
CLV/PM
V/f OLV
SIEP_C710636_02B_1_0.book 487 ージ 015年11月25日 水曜日 午後4時56