B.3 Parameter Table
498 YASKAWA ELECTRIC SIEP C710636 02B YASKAWA U1000 Technical Manual
16 Motor 2 Selection
Open: Motor 1 (E1-, E2-)
Closed: Motor 2 (E3-, E4-)
271
17 Fast Stop (N.C.)
Open: Decelerates to stop at the Fast Stop time set to C1-09.
270
18 Timer Function Input
Triggers the timer set up by parameters b4-01 and b4-02. Must be set in conjunction with the timer function output
(H2- = 12).
271
19 PID Disable
Open: PID control enabled
Closed: PID control disabled
271
1A Accel/Decel Time Selection 2
Used in conjunction with an input terminal set for “Accel/decel time selection 1” (H1- = 7), and allows the
drive to switch between accel/decel times 3 and 4.
272
1B Program Lockout
Open: Parameters cannot be edited (except for U1-01 if the reference source is assigned to the digital operator).
Closed: Parameters can be edited and saved.
272
1E Reference Sample Hold
Closed: Samples the analog frequency reference and operates the drive at that speed.
272
20 to 2F External Fault
20: N.O., Always detected, ramp to stop
21: N.C., Always detected, ramp to stop
22: N.O., During run, ramp to stop
23: N.C., During run, ramp to stop
24: N.O., Always detected, coast to stop
25: N.C., Always detected, coast to stop
26: N.O., During run, coast to stop
27: N.C., During run, coast to stop
28: N.O., Always detected, Fast Stop
29: N.C., Always detected, Fast Stop
2A: N.O., During run, Fast Stop
2B: N.C., During run, Fast Stop
2C: N.O., Always detected, alarm only (continue running)
2D: N.C., Always detected, alarm only (continue running)
2E: N.O., During run, alarm only (continue running)
2F: N.C., During run, alarm only (continue running)
272
30 PID Integral Reset
Closed: Resets the PID control integral value.
273
31 PID Integral Hold
Open: Performs integral operation.
Closed: Maintains the current PID control integral value.
273
32 Multi-Step Speed Reference 4
Used in combination with input terminals set to Multi-Step Speed Reference 1, 2, and 3. Use parameters d1-09 to
d1-16 to set reference values.
273
34 PID Soft Starter Cancel
Open: PID soft starter is enabled.
Closed: Disables the PID soft starter b5-17.
273
35 PID Input Level Selection
Closed: Inverts the PID input signal
273
40
Forward Run Command (2-wire
Sequence)
Open: Stop
Closed: Forward run
Note: Cannot be set together with settings 42 or 43.
273
41
Reverse Run Command (2-wire
Sequence)
Open: Stop
Closed: Reverse run
Note: Cannot be set together with settings 42 or 43.
273
42 Run Command (2-wire Sequence 2) Open: Stop
Closed: Run
Note: Cannot be set together with settings 40 or 41.
273
H1 Multi-Function Digital Input Selections
H1-
Setting
Function Description Page
OLV/PM AOLV/PM
CLV
V/f w/PG
CLV/PM
V/f OLV
All Modes
All Modes
All Modes
All Modes
All Modes
All Modes
All Modes
All Modes
All Modes
All Modes
All Modes
All Modes
All Modes
All Modes
All Modes
SIEP_C710636_02B_1_0.book 498 ページ 2015年11月25日 水曜日 午後4時56分