B.3 Parameter Table
YASKAWA ELECTRIC
SIEP C710636 02B YASKAWA U1000 Technical Manual 499
Parameter List
B
43
FWD/REV Command (2-wire Sequence
2)
Open: Forward
Closed: Reverse
Note: Determines motor direction, but does not issue a Run command. Cannot be set together with settings 40 or
41.
273
44 Offset Frequency 1
Closed: Adds d7-01 to the frequency reference.
273
45 Offset Frequency 2
Closed: Adds d7-02 to the frequency reference.
273
46 Offset Frequency 3
Closed: Adds d7-03 to the frequency reference.
273
47 Node Setup
Closed: Node setup for SI-S3 enabled.
274
60 DC Injection Braking Command
Closed: Triggers DC Injection Braking.
274
61 External Speed Search Command 1
Closed: Activates Current Detection Speed Search from the maximum output frequency (E1-04).
274
62 External Speed Search Command 2
Closed: Activates Current Detection Speed Search from the frequency reference.
274
63 Field Weakening
Closed: The drive performs Field Weakening control as set for d6-01 and d6-02.
274
67 Communications Test Mode
Tests the MEMOBUS/Modbus RS-485/422 interface. Displays “PASS” if the test completes successfully.
274
6A Drive Enable
Open: Drive disabled. If this input is opened during run, then the drive will stop as specified by b1-03.
Closed: Ready for operation.
274
71 Speed/Torque Control Switch
Open: Speed Control
Closed: Torque Control
274
72 Zero Servo
Closed: Zero Servo enabled
274
75 Up 2 Command
Used to control the bias added to the frequency reference by the Up/Down 2 function. The Up 2 and Down 2
commands must always be used in conjunction with one another.
274
76 Down 2 Command 274
77 ASR Gain Switch
Open: ASR proportional gain 1 (C5-01)
Closed: ASR proportional gain 2 (C5-03)
275
78
External Torque Reference Polarity
Inversion
Open: Forward torque reference
Closed: Reverse polarity
275
7E
Forward/Reverse Detection (V/f Control
with Simple PG feedback)
Direction of rotation detection (for V/f with Simple PG Feedback)
275
90 to 97 DriveWorksEZ Digital Inputs 1 to 8
Reserved for DWEZ input functions
275
9F DriveWorksEZ Disable
Open: DWEZ enabled
Closed: DWEZ disabled
275
H1 Multi-Function Digital Input Selections
H1-
Setting
Function Description Page
All Modes
All Modes
All Modes
All Modes
All Modes
OLV/PM AOLV/PM
CLV
V/f w/PG
CLV/PM
V/f OLV
OLV/PM AOLV/PM
CLV
V/f w/PG
CLV/PM
V/f OLV
OLV/PM AOLV/PM
CLV
V/f w/PG
CLV/PM
V/f OLV
OLV/PM AOLV/PM
CLV
V/f w/PG
CLV/PM
V/f OLV
All Modes
All Modes
OLV/PM AOLV/PM
CLV
V/f w/PG
CLV/PM
V/f OLV
OLV/PM AOLV/PM
CLV
V/f w/PG
CLV/PM
V/f OLV
All Modes
OLV/PM AOLV/PM
CLV
V/f w/PG
CLV/PM
V/f OLV
OLV/PM AOLV/PM
CLV
V/f w/PG
CLV/PM
V/f OLV
OLV/PM AOLV/PM
CLV
V/f w/PG
CLV/PM
V/f OLV
All Modes
All Modes
SIEP_C710636_02B_1_0.book 499 ージ 015年11月25日 水曜日 午後4時56