B.3 Parameter Table
500 YASKAWA ELECTRIC SIEP C710636 02B YASKAWA U1000 Technical Manual
H2: Multi-Function Digital Outputs
No.(Addr.) Name Description Setting Page
H2-01
(40BH)
Terminal M1-M2 Function
Selection (Relay)
Assigns a function to the multi-function digital outputs.
Refer to H2 Multi-Function Digital Output Settings on page 500 for a description of setting
values.
Default: 0
Min: 0
Max: 192
276
H2-02
(40CH)
CIMR-UA, CIMR-UD,
CIMR-UT:
Terminal P1-PC Function
Selection (Open-collector)
Default: 1
Min: 0
Max: 192
276
CIMR-UB:
Terminal M3-M4 Function
Selection (Relay)
H2-03
(40DH)
CIMR-UA, CIMR-UD,
CIMR-UT:
Terminal P2-PC Function
Selection (Open-collector)
Default: 2
Min: 0
Max: 192
276
CIMR-UB:
Terminal M5-M6 Function
Selection (Relay)
H2-06
(437H)
Power Consumption Output Unit
Selection
Sets the units for the output signal when one of the multi-function terminals is set to power
consumption pulse output (H2-01, H2-02, or H2-03 = 39) or regenerated power pulse output
(H2-01, H2-02, or H2-03 = 3A). Outputs a 200 ms pulse signal when the watt-hour counter
increases by the units selected.
0: 0.1 kWh units
1: 1 kWh units
2: 10 kWh units
3: 100 kWh units
4: 1000 kWh units
Note: The Setting range is 1 to 4 in the drive software versions S1014 and earlier.
Default: 1
Min: 0
Max: 4
285
H2-07
(B3AH)
Memobus Regs1 Address Select
Sets the addresses of the MEMOBUS/Modbus registers from which data will be sent to contact
outputs 62 and 162.
Default: 1
Min: 1
Max: 1FFFH
285
H2-08
(B3BH)
Memobus Regs1 Bit Select
Sets the bits for the MEMOBUS/Modbus registers from which data will be sent to contact
outputs 62 and 162.
Default: 0
Min: 0
Max: FFFFH
285
H2-09
(B3CH)
Memobus Regs2 Address Select
Sets the addresses of the MEMOBUS/Modbus registers from which data will be sent to contact
outputs 63 and 163.
Default: 1
Min: 1
Max: 1FFFH
285
H2-10
(
B3DH)
Memobus R
egs2 Bit Select
Sets the bits for the MEMOBUS/Modbus registers from which data will be sent to contact
outputs 63 and 163.
Default: 0
Min: 0
Max: FFFFH
285
H2 Multi-Function Digital Output Settings
H2-
Setting
Function Description Page
0 During Run
Closed: A Run command is active or voltage is output.
276
1 Zero Speed
Open: Output speed is greater than or equal to the value of E1-09 (Minimum Output Frequency) or b2-01 (DC Injection
Braking Start Frequency).
Closed: Output frequency is less than the value of E1-09 (Minimum Output Frequency) or b2-01 (DC Injection Braking
Start Frequency).
277
2 Speed Agree 1
Closed: Output frequency equals the speed reference (plus or minus the hysteresis set to L4-02).
277
3 User-set Speed Agree 1
Closed: Output frequency and speed reference equal L4-01 (plus or minus the hysteresis set to L4-02).
277
4 Frequency Detection 1
Closed: Output frequency is less than or equal to the value in L4-01 with hysteresis determined by L4-02.
278
5 Frequency Detection 2
Closed: Output frequency is greater than or equal to the value in L4-01 with hysteresis determined by L4-02.
278
6 Drive Ready
Closed: Power up is complete and the drive is ready to accept a Run command.
279
7 During Power Supply Voltage Fault
Closed: One of the following faults will occur: AUv (Power Supply Undervoltage), Uv (Undervoltage). or Fdv (Power
Supply Frequency Fault).
279
All Modes
All Modes
All Modes
All Modes
All Modes
All Modes
All Modes
All Modes
All Modes
All Modes
All Modes
All Modes
All Modes
All Modes