B.3 Parameter Table
YASKAWA ELECTRIC
SIEP C710636 02B YASKAWA U1000 Technical Manual 501
Parameter List
B
8 During Baseblock (N.O.)
Closed: Drive has entered the baseblock state (no output voltage).
279
9 Frequency Reference Source
Open: External Reference 1 or 2 supplies the frequency reference (set in b1-01 or b1-15).
Closed: Digital operator supplies the frequency reference.
279
A Run Command Source
Open: External Reference 1 or 2 supplies the Run command (set in b1-02 or b1-16).
Closed: Digital operator supplies the Run command.
279
B Torque Detection 1 (N.O.)
Closed: An overtorque or undertorque situation has been detected.
279
C Frequency Reference Loss
Closed: Analog frequency reference has been lost.
Frequency reference loss is detected when the frequency reference drops below 10% of the reference within 400 ms.
280
EFault
Closed: Fault occurred (this excludes faults CPF00 and CPF01).
280
F Through Mode
Select this setting when the terminal is not used or when using the terminal in the pass-through mode.
280
10 Minor Fault
Closed: An alarm has been triggered.
280
11 Fault Reset Command Active
Closed: The drive has received a reset command from the multi-function input terminals or from serial network, or the
digital operators RESET key has been pressed.
280
12 Timer Output
Closed: Timer output.
280
13 Speed Agree 2
Closed: When drive output frequency equals the frequency reference ±L4-04.
280
14 User-set Speed Agree 2
Closed: When the drive output frequency is equal to the value in L4-03 ±L4-04.
281
15 Frequency Detection 3
Closed: When the drive output frequency is less than or equal to the value in L4-03 ±L4-04.
281
16 Frequency Detection 4
Closed: When the output frequency is greater than or equal to the value in L4-03 ±L4-04.
282
17 Torque Detection 1 (N.C.)
Open: Overtorque or undertorque has been detected.
279
18 Torque Detection 2 (N.O.)
Closed: Overtorque or undertorque has been detected.
279
19 Torque Detection 2 (N.C.)
Open: Overtorque or undertorque has been detected.
279
1A During Reverse
Closed: Drive is running in the reverse direction.
282
1B During Baseblock (N.C.)
Open: Drive has entered the baseblock state (no output voltage).
282
1C Motor 2 Selection
Closed: Motor 2 is selected by a digital input (H1- = 16)
282
1D During Regeneration
Closed: Motor is regenerating energy into the drive.
283
1E Restart Enabled
Closed: An automatic restart is performed
283
1F Motor Overload Alarm (oL1)
Closed: oL1 is at 90% of its trip point or greater. An oH3 situation also triggers this alarm.
283
20 Drive Overheat Pre-alarm (oH)
Closed: Heatsink temperature exceeds the parameter L8-02 value.
283
H2 Multi-Function Digital Output Settings
H2-
Setting
Function Description Page
All Modes
All Modes
All Modes
All Modes
All Modes
All Modes
All Modes
All Modes
All Modes
All Modes
All Modes
All Modes
All Modes
All Modes
All Modes
All Modes
All Modes
All Modes
All Modes
OLV/PM AOLV/PM
CLV
V/f w/PG
CLV/PM
V/f OLV
OLV/PM AOLV/PM
CLV
V/f w/PG
CLV/PM
V/f OLV
All Modes
All Modes
All Modes
SIEP_C710636_02B_1_0.book 501 ージ 015年11月25日 水曜日 午後4時56