B.3 Parameter Table
502 YASKAWA ELECTRIC SIEP C710636 02B YASKAWA U1000 Technical Manual
22 Mechanical Weakening Detection
Closed: Mechanical weakening detected.
283
2F Maintenance Period
Closed: Cooling fan, electrolytic capacitors,or the soft charge bypass relay may require maintenance.
283
30 During Torque Limit
Closed: When the torque limit has been reached.
283
31 During Speed Limit
Closed: Speed limit has been reached.
283
32
During Speed Limit in Torque
Control
Closed: Speed limit has been reached while using Torque Control.
283
33 Zero Servo Complete
Closed: Zero Servo operation has finished.
283
37 During Frequency Output
Open: No frequency output from drive if stopped, with baseblock, or with DC injection braking during initial
excitation.
Closed: Drive is outputting a frequency.
283
38 Drive Enabled
Closed: Multi-function input set for “Drive enable” is closed (H1- = 6A)
284
39 Power Consumption Pulse Output
Outputs a pulse to indicate the power consumption. Output units are determined by H2-06. Outputs a pulse every 200
ms to indicate the kWh count.
284
3A Regenerated Power Pulse Output
Outputs a pulse to indicate the regenerated power. Output units are determined by H2-06. Outputs a pulse every 200 ms
to indicate the kWh count.
284
3C LOCAL/REMOTE Status
Open: REMOTE
Closed: LOCAL
284
3D During Speed Search
Closed: Speed Search is being executed.
284
3E PID Feedback Low
Closed: PID feedback level is too low.
284
3F PID Feedback High
Closed: The PID feedback level is too high.
284
4C During Fast Stop
Closed: A Fast Stop command has been entered from the operator or input terminals.
284
4D oH Pre-alarm Time Limit
Closed: oH pre-alarm time limit has passed.
284
60 Internal Cooling Fan Alarm
Closed: Internal cooling fan alarm
284
61 Rotor Position Detection Complete
Closed: Drive has successfully detected the rotor position of the PM motor.
284
62
Memobus Regs1 (It selects it with
H2-07 and H2-08.) The contact output is closed if any of the bits that are specified by H2-08 for the MEMOBUS/Modbus register address
that is set in H2-07 turns on.
285
63
Memobus Regs2 (It selects it with
H2-09 and H2-10.)
The contact output is closed if any of the bits that are specified by H2-10 for the MEMOBUS/Modbus register address
that is set in H2-09 turns on.
285
64 During Commercial Power Operation
Closed: Operating on commercial power.
285
H2 Multi-Function Digital Output Settings
H2-
Setting
Function Description Page
All Modes
All Modes
OLV/PM AOLV/PM
CLV
V/f w/PG
CLV/PM
V/f OLV
OLV/PM AOLV/PM
CLV
V/f w/PG
CLV/PM
V/f OLV
OLV/PM AOLV/PM
CLV
V/f w/PG
CLV/PM
V/f OLV
OLV/PM AOLV/PM
CLV
V/f w/PG
CLV/PM
V/f OLV
All Modes
All Modes
All Modes
All Modes
All Modes
All Modes
All Modes
All Modes
All Modes
All Modes
All Modes
OLV/PM AOLV/PM
CLV
V/f w/PG
CLV/PM
V/f OLV
All Modes
All Modes
OLV/PM AOLV/PM
CLV
V/f w/PG
CLV/PM
V/f OLV