B.3 Parameter Table
520 YASKAWA ELECTRIC SIEP C710636 02B YASKAWA U1000 Technical Manual
T1-04
(704H)
Motor Rated Current
Sets the motor rated current as specified on the motor nameplate.
Default:
<6>
Min: 10% of drive rated
current
Max: 150% of drive
rated current
162
T1-05
(705H)
Motor Base Frequency
Sets the rated frequency of the motor as specified on the motor nameplate.
Default:
<46>
Min: 0.0 Hz
Max: 400.0 Hz
162
T1-06
(706H)
Number of Motor Poles
Sets the number of motor poles as specified on the motor nameplate.
Default: 4
Min: 2
Max: 48
162
T1-07
(707H)
Motor Base Speed
Sets the rated speed of the motor as specified on the motor nameplate.
Default:
<47>
Min: 0 min
-1
Max: 24000 min
-1
163
T1-08
(708H)
PG Number of Pulses Per
Revolution
Set the number of pulses per revolution for the PG being used (pulse generator or encoder).
Default:
<45>
Min: 0 ppr
Max: 60000 ppr
163
T1-09
(709H)
Motor No-Load Current
(Stationary Auto-Tuning)
Sets the no-load current for the motor.
After setting the motor capacity to T1-02 and the motor rated current to T1-04, this parameter
will automatically display the no-load current for a standard 4 pole Yaskawa motor. Enter the
no-load current as indicated on the motor test report.
Default: –
Min: 0 A
Max: T1-04
<72>
163
T1-10
(70AH)
Motor Rated Slip
(Stationary Auto-Tuning)
Sets the motor rated slip.
After setting the motor capacity to T1-02, this parameter will automatically display the motor
slip for a standard 4 pole Yaskawa motor. Enter the motor slip as indicated on the motor test
report.
Default: –
Min: 0.00 Hz
Max: 20.00 Hz
163
T1-11
(70BH)
Motor Iron Loss
Sets the iron loss for determining the Energy Saving coefficient.
The value is set to E2-10 (motor iron loss) set when the power is cycled. If T1-02 is changed, a
default value appropriate for the motor capacity that was entered will appear.
Default: 14 W
<38>
Min: 0 W
Max: 65535 W
163
<6> Default setting value varies by the drive model (o2-04).
<9> Default setting value is dependent on the drive model (o2-04) and the Drive Duty (C6-01).
<10> Default setting is determined by the control mode (A1-02).
<18> Values shown here are for 200 V class drives. Double the value when using a 400 V class drive.
<37> The availability of certain Auto-Tuning methods depends on the control mode selected for the drive.
<38> Default setting value differs depending on the motor code value and motor parameter settings.
<45> Regional default settings
Setting 600 ppr: Japan (Model code: CIMR-UA), India (Model code: CIMR-UD), and Asia (Model code: CIMR-UT)
Setting 1024 ppr: China (Model code: CIMR-UB)
<46> Regional default settings
Setting 60.0 Hz: Japan (Model code: CIMR-UA), India (Model code: CIMR-UD), and Asia (Model code: CIMR-UT)
Setting 50.0 Hz: China (Model code: CIMR-UB)
<47> Regional default settings
Setting 1750 min
-1
: Japan (Model code: CIMR-UA), India (Model code: CIMR-UD), and Asia (Model code: CIMR-UT)
Setting 1450 min
-1
: China (Model code: CIMR-UB)
<72> Display is in the following units.
CIMR-U20028, 20042, and 40011 to 40027: 0.01 A units
CIMR-U20054 to 20248, and 40034 to 40930: 0.1 A units
No. (Addr.) Name Description Setting Page
OLV/PM AOLV/PM
CLV
V/f w/PG
CLV/PM
V/f OLV
OLV/PM AOLV/PM
CLV
V/f w/PG
CLV/PM
V/f OLV
OLV/PM AOLV/PM
CLV
V/f w/PG
CLV/PM
V/f OLV
OLV/PM AOLV/PM
CLV
V/f w/PG
CLV/PM
V/f OLV
OLV/PM AOLV/PM
CLV
V/f w/PG
CLV/PM
V/f OLV
OLV/PM AOLV/PM
CLV
V/f w/PG
CLV/PM
V/f OLV
OLV/PM AOLV/PM
CLV
V/f w/PG
CLV/PM
V/f OLV
OLV/PM AOLV/PM
CLV
V/f w/PG
CLV/PM
V/f OLV
SIEP_C710636_02B_1_0.book 520 ージ 015年11月25日 水曜日 午後4時56

Table of Contents

Other manuals for YASKAWA U1000 Series

Related product manuals