Point
Numb
er
Point
Type
Point Name
Factory
Default
(SI
Units)
Eng. Units
(SI Units)
Slope
(SI
Units)
Intercept
(SI Units)
On Text Off Text Parameter
78 LDI MF IN 4 MON OFF 1 0 ON OFF U1-10 (Bit 5)
79 LAI PID DEVIATE 0 % 0.01 0 U5-02
80 LAO PID I LIMIT 100 % 0.1 0 b5-04
81 LAO PID UP LIMIT 100 % 0.1 0 b5-06
82 LAO PID OFFS ADJ 100 % 0.1 -100 b5-07
83 LAO PID PRI DYTM 0 s 0.1 0 b5-08
84 LAO PID FB RMDS 0 1 0 b5-12
85 LAO PID FB RMDL 0 % 1 0 b5-13
86 LAO PID FB RMDT 1 s 0.1 0 b5-14
87 LAI PID OUT CAP 0 % 0.01 0 U5-14
88 LAI PID REF 0 % 0.01 0 U5-04
89 LAI COMM ERR CD 0 1 0 U1-19
90 LDO
COMM FLT
ENA
ENABLE 1 0
ENABL
E
DISABLE H5-05
91 LAO CBL LOSS FRQ 0 Hz 0.01 0 d1-04
92 LAO CBL LOSS TMR 2 s 0.1 0 H5-09
93 LDI OK.FAULT OK 1 0 FAULT OK U1-12 (Bit 7)
94 LDO RESET FAULT NO 1 0 RESET NO
95 LDI
DRV COMM
ERR
NO FLT 1 0 FAULT NO FLT
96 LDO EXTERNAL FLT OK 1 0 FAULT OK
97 LDI MF IN 5 MON OFF 1 0 ON OFF U1-10 (Bit 6)
99 LAI
ERROR
STATUS
0 1 0 U1-19
<1> Set H1-03 to 70 , Drive Enable2, for pt 35 to work properly.
C.5 APOGEE FLN Point Database
YASKAWA SIEP YAIZ1U 03B YASKAWA AC Drive – Z1000 Programming Manual
277
C
APOGEE FLN (P1)
Communications