EasyManua.ls Logo

YASKAWA Z1000 CIMR-ZU*A Series

YASKAWA Z1000 CIMR-ZU*A Series
340 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Register No. Contents
00CCH
Alarm Contents 6
bit 0 Output Voltage Detection Fault (VoF)
bit 1 Reserved
bit 2 Capacitor Maintenance Time (LT-3)
bit 3 to C Reserved
bit D Motor Underload Protection (UL6)
bit E Waiting for Run (WrUn)
bit F Reserved
00CDH Reserved
00CEH
Alarm Contents 7
bit 2 Time Not Set (TIM)
bit 3 Operator Battery Low (bAT)
bit 4 Time Data Error (TdE)
bit 5 External Fan Fault (Fn1)
bit 6 Emergency Override Forward Run (EoF)
bit 7 Emergency Override Reverse Run (Eor)
00CFH Reserved
00D0H
CPF Contents 1
bit 0, 1 Reserved
bit 2 A/D Conversion Error (CPF02)
bit 3 PWM Data Fault (CPF03)
bit 4, 5 Reserved
bit 6 EEPROM Memory Data Error (CPF06)
bit 7 Terminal Board Connection Error (CPF07)
bit 8 EEPROM Serial Communications Fault (CPF08)
bit 9 to F Reserved
00D1H
CPF Contents 2
bit 0 to 3 Reserved
bit 4 Hardware fault at power up (CPF20)
bit 5 Hardware fault at communication start up (CPF21)
bit 6 A/D Conversion Fault (CPF22)
bit 7 PWM Feedback Fault (CPF23)
bit 8 Drive Unit Signal Fault (CPF24)
bit 9 to F Reserved
00D2H Reserved
00D3H to 00D7H
oFA0o Contents (CN5)
00D8H
oFA0o Contents (CN5)
bit 0 Option Compatibility Error (oFA00)
bit 1 Option not properly connected (oFA01)
bit 2 to 4 Reserved
bit 5 A/D Conversion Error (oFA05)
bit 6 Option Response Error (oFA06)
bit 7 to F Reserved
E.9 MEMOBUS/Modbus Data Table
YASKAWA SIEP YAIZ1U 03B YASKAWA AC Drive – Z1000 Programming Manual
323
E
MEMOBUS/Modbus
Communications

Table of Contents

Related product manuals