Setting 52: Sequence Timer 2 Active
Sequence Timer 2 is active.
Setting 53: Sequence Timer 3 Active
Sequence Timer 3 is active.
Setting 54: Sequence Timer 4 Active
Sequence Timer 4 is active.
Setting 58: Underload Detection
Underload is detected when the output current falls below the underload detection level defined by L6-14 and L6-02.
Setting 60: Internal Cooling Fan Alarm
The output closes when the drive internal cooling fan has failed.
Setting 71: Secondary PI Feedback Low
The PI2 feedback level is too low.
Setting 72: Secondary PI Feedback High
The PI2 feedback level is too high.
Setting A4: BP Drive Relay
Line voltage is being supplied to the drive, and the motor is being run via the drive.
Note: Available in V/f control mode.
Setting A5: BP Bypass Relay
Line voltage is being supplied directly to the motor.
Note: Available in V/f control mode.
Setting A6: BP BAS Interlock Relay
Actuation signal for options dampers.
Note: Available in V/f control mode.
Setting A9: Relay Operator Control
F1 (F2) key toggle relay is output.
Setting B2: BAS Interlock Relay Contact
A Run command is active or voltage is output. Actuation signal for damper.
Setting 100 to 1B2: Functions 0 to B2 with Inverse Output
These settings have the same function as settings 0 to B2, but with inverse output. Set as 1oo, where the “1” indicates inverse
output and the last two digits specify the setting number of the function.
Examples:
Set 108 for inverse output of “8: During Baseblock (N.O.)”.
Set 14A for inverse output of “4A: During KEB Operation”.
1.7 H: Terminal Functions
YASKAWA SIEP YAIZ1U 03B YASKAWA AC Drive – Z1000 Programming Manual
91