Bit Name Value Information
(continued)
9 Limit 1 Operation is limited by any of the torque limits.
0 Operation is within the torque limits.
10 Above limit 1 Actual speed exceeds limit defined by parameter 19.08 Above speed
lim.
0 Actual speed is within the defined limits.
11 Ext2 act 1 External control location EXT2 is active.
0 External control location EXT1 is active.
12 Local fb 1 Fieldbus local control is active.
0 Fieldbus local control is inactive.
13 Zero
speed
1 Drive speed is below limit defined by parameter 19.06 Zero speed
limit.
0 Drive has not reached zero speed limit.
14 Rev act 1 Drive is running in reverse direction.
0 Drive is running in forward direction.
15 Reserved
16 Fault 1 A fault is active. See chapter Fault tracing on page 313.
0 No fault is active.
17 Local
panel
1 Local control is active, i.e. the drive is controlled from PC tool or
control panel.
0 Local control is inactive.
18…26 Reserved
27 Request ctl 1 Control Word is requested from fieldbus.
0 Control Word is not requested from fieldbus.
28 SW B28 Programmable control bits (unless fixed by the used profile). See parameters
50.08…50.11 and the user manual of the fieldbus adapter.
29 SW B29
30 SW B30
31 SW B31