164 Parameters
16
16 System
Local lock and parameter lock settings; parameter restore;
user parameter set load/save; parameter change log reset;
parameter list settings; unit of power selection; application
macro display.
16.01 Local lock Selects the source for disabling local control (Take/Release
button in the PC tool, LOC/REM key of the panel).
0 = Local control enabled.
1 = Local control disabled.
WARNING! Before activating, ensure that the control
panel is not needed for stopping the drive!
Const Bit pointer setting (see Terms and abbreviations on page
109).
-
Pointer
16.02 Parameter lock Selects the state of the parameter lock. The lock prevents
parameter changing.
Locked Locked. Parameter values cannot be changed from the
control panel. The lock can be opened by entering the valid
code into parameter 16.03 Pass code.
0
Open The lock is open. Parameter values can be changed. 1
Not saved The lock is open. Parameter values can be changed, but the
changes will not be stored at power switch-off.
2
16.03 Pass code Selects the pass code for the parameter lock (see parameter
16.02 Parameter lock).
After entering 358 at this parameter, parameter 16.02
Parameter lock can be adjusted. The value reverts back to 0
automatically.
0 … 2147483647 Pass code for parameter lock. 1 = 1
16.04 Param restore Restores the original settings of the application, i.e.
parameter factory default values.
Note: This parameter cannot be changed while the drive is
running.
Done Restoring is completed. 0
Restore defs All parameter values are restored to default values, except
motor data, ID run results, and fieldbus adapter and drive-to-
drive link configuration data.
1
Clear all All parameter values are restored to default values, including
motor data, ID run results, and fieldbus adapter and drive-to-
drive link configuration data. PC tool communication is
interrupted during the restoring. Drive CPU is re-booted after
the restoring is completed.
2
16.07 Param save Saves the valid parameter values to the permanent memory.
Note: A new parameter value is saved automatically when
changed from the PC tool or panel but not when altered
through a fieldbus adapter connection.
Done Save completed. 0
Save Save in progress. 1