Parameters 163
15.17 AO3 src max Defines the real value of the signal (selected by parameter
15.13 AO3 src) that corresponds to the maximum AO3
output value (defined by parameter 15.15 AO3 out max).
-32768.000 …
32768.000
Real signal value corresponding to maximum AO3 output
value.
1000 = 1
15.18 AO3 src min Defines the real value of the signal (selected by parameter
15.13 AO3 src) that corresponds to the minimum AO3 output
value (defined by parameter 15.16 AO3 out min). See
parameter 15.17 AO3 src max.
-32768.000 …
32768.000
Real signal value corresponding to minimum AO3 output
value.
1000 = 1
15.25 AO ctrl word Defines how a signed source is processed before output.
No. Name/Value Description FbEq
I
AO3
(mA)
15.15
15.16
15.17 15.18
15.1715.18
15.15
15.16
Signal (real)
selected by
par. 15.13
I
AO3
(mA)
Signal (real)
selected by
par. 15.13
Bit Name Information
0AO1 func
1 = AO1 is bipolar
0 = AO1 is absolute value of source
1AO2 func
1 = AO2 is bipolar
0 = AO2 is absolute value of source