126 Parameters
05.35 kWh December Energy consumed during last December. 1 = 1 kWh
05.36 First in order The first pump in the current Autochange sequence. 1 = 1
05.37 Time autochg Time elapsed since last Autochange. 1 = 1 ms
05.39 Next start node (Only valid when the drive is master.) Node number of the
next drive to be started.
1 = 1
06
06 Drive status
Drive status words.
06.01 Status word1 Status word 1 of the drive. -
No. Name/Value Description FbEq
Bit Name Information
0 Ready 1 = Drive is ready to receive start command.
0 = Drive is not ready.
1 Enabled 1 = External run enable signal is received.
0 = No external run enable signal is received.
2 Started 1 = Drive has received start command.
0 = Drive has not received start command.
3 Running 1 = Drive is modulating.
0 = Drive is not modulating.
4Em off
(off2)
1 = Emergency OFF2 is active.
0 = Emergency OFF2 is inactive.
5Em stop
(off3)
1 = Emergency OFF3 (ramp stop) is active.
0 = Emergency OFF3 is inactive.
6 Ack startinh 1 = Start inhibit is active.
0 = Start inhibit is inactive.
7 Alarm 1 = Alarm is active. See chapter Fault tracing.
0 = No alarm is active.
8 Ext2 act 1 = External control EXT2 is active.
0 = External control EXT1 is active.
9 Local fb 1 = Fieldbus local control is active.
0 = Fieldbus local control is inactive.
10 Fault 1 = Fault is active. See chapter Fault tracing.
0 = No fault is active.
11 Local panel 1 = Local control is active, ie. drive is controlled from PC tool or control
panel.
0 = Local control is inactive.
12 Fault(-1) 1 = No fault is active.
0 = Fault is active. See chapter Fault tracing.
13…15 Reserved