Parameters 125
05.02 Trad pump cmd Pump control word. The bits of this parameter can be used
to control the relay outputs that switch pumps on and off.
-
05.03 Trad master In traditional pump control, the number of the pump that is
directly controlled by the drive.
1 = 1
05.04 Nbr aux pumps on Number of auxiliary pumps running. 1 = 1
05.05 Flow act Actual flow as calculated by the drive. See parameter group
80 Flow calculation (page 267).
100 = 1 m
3
/h
05.06 Flow by head Flow calculated on the basis of the HQ performance curve.
See parameter group 80 Flow calculation (page 267).
100 = 1 m
3
/h
05.07 Flow by power Flow calculated on the basis of the PQ performance curve.
See parameter group 80 Flow calculation (page 267).
100 = 1 m
3
/h
05.08 Total flow Total calculated flow. Stored when the drive is not powered.
Can be reset using parameter 80.33 Sum flow reset.
1 = 1 m
3
05.09 Bypass ref Reference used when parameter 75.01 Operation mode is
set to Reg bypass.
10 = 1 rpm
05.10 Speed ref Final speed reference from the pump control logic. 10 = 1 rpm
05.20 kWh current read Energy consumed during the current period.
The length of the period is set by parameter 83.02 Mon
period.
1 = 1 kWh
05.21 kWh prev read Energy consumed during the last completed period. The
length of the period is set by parameter 83.02 Mon period.
1 = 1 kWh
05.22 kWh posprev read Energy consumed during the period before the last
completed period. The length of the period is set by
parameter 83.02 Mon period.
1 = 1 kWh
05.23 kWh cur mon read Energy consumed during the current month. 1 = 1 kWh
05.24 kWh January Energy consumed during last January. 1 = 1 kWh
05.25 kWh February Energy consumed during last February. 1 = 1 kWh
05.26 kWh March Energy consumed during last March. 1 = 1 kWh
05.27 kWh April Energy consumed during last April. 1 = 1 kWh
05.28 kWh May Energy consumed during last May. 1 = 1 kWh
05.29 kWh June Energy consumed during last June. 1 = 1 kWh
05.30 kWh July Energy consumed during last July. 1 = 1 kWh
05.31 kWh August Energy consumed during last August. 1 = 1 kWh
05.32 kWh September Energy consumed during last September. 1 = 1 kWh
05.33 kWh October Energy consumed during last October. 1 = 1 kWh
05.34 kWh November Energy consumed during last November. 1 = 1 kWh
No. Name/Value Description FbEq
Bit Name
0 Pump 1. Note: The setting of parameter 78.02 Autochg trad determines whether “Pump
1” refers to the first pump of the station, or the first auxiliary pump of the station.
1 Pump 2
2 Pump 3
3 Pump 4
4 Pump 5
5 Pump 6
6 Pump 7
7 Pump 8

Table of Contents

Other manuals for ABB ACQ810

Related product manuals