Program features 65
Control interfaces
Programmable analog inputs
The drive has two programmable analog inputs. Each of the inputs can be
independently set as a voltage (0/2…10 V or -10…10 V) or current (0/4…20 mA)
input by a jumper on the JCU Control Unit. Each input can be filtered, inverted and
scaled. The number of analog inputs can be increased by using FIO-xx I/O
extensions.
See also Pressure sensor connection examples on page 108.
Settings
Parameter group 13 Analogue inputs (page 142).
Diagnostics
Parameters 02.04…02.13 (page 113).
Programmable analog outputs
The drive has two programmable current-type analog outputs. Each output can be
filtered, inverted and scaled. The number of analog outputs can be increased by
using FIO-xx I/O extensions.
Settings
Parameter group 15 Analogue outputs (page 158).
Diagnostics
Parameters 02.16…02.19 (page 114).
Programmable digital inputs and outputs
The drive has five digital inputs, a digital start interlock input, and two digital
input/outputs.
One digital input (DI5) doubles as a PTC thermistor input. See section Thermal motor
protection on page 78.
One of the digital input/outputs can be used as a frequency input, the other as a
frequency output.
The number of digital input/outputs can be increased by using FIO-xx I/O extensions.
Settings
Parameter group 14 Digital I/O (page 148).