Parameters 173
AI2 scaled 02.07 AI2 scaled (see page 113). 1073742343
Freq in 02.20 Freq in (see page 114). 1073742356
FBA ref1 02.26 FBA main ref1 (see page 118). 1073742362
FBA ref2 02.27 FBA main ref2 (see page 118). 1073742363
Panel 02.34 Panel ref (see page 118). 1073742370
EFB ref1 02.38 EFB main ref1 (see page 122). 1073742374
EFB ref2 02.39 EFB main ref2 (see page 122). 1073742375
Pointer Value pointer setting (see Terms and abbreviations on page
109).
-
21.05 Speed share Defines the scaling factor for the speed reference (the speed
reference is multiplied by the defined value).
-8.000 …8.000 Speed reference scaling factor. 1000 = 1
21.09 SpeedRef min abs Defines the absolute minimum limit for the speed reference.
0 … 30000 rpm Absolute minimum limit for speed reference. 1 = 1 rpm
22
22 Speed ref ramp
Speed reference and emergency stop (OFF3) ramp settings.
22.02 Acc time Defines acceleration time as the time required for the speed
to change from zero to the speed value defined by
parameter 19.01 Speed scaling.
If the speed reference increases faster than the set
acceleration rate, the motor speed will follow the
acceleration rate.
If the speed reference increases slower than the set
acceleration rate, the motor speed will follow the reference
signal.
If the acceleration time is set too short, the drive will
automatically prolong the acceleration in order not to exceed
the drive torque limits.
0.000 … 1800.000 s Acceleration time. 1000 = 1 s
No. Name/Value Description FbEq
20.01
Maximum speed
21.09
SpeedRef min abs
-(21.09
SpeedRef min abs)
20.02
Minimum speed
Speed reference
Limited speed reference