294 Additional parameter data
Parameter groups 10…99
No. Name Type
Data
len.
Range Unit
Default (Factory
def macro)
10 Start/stop/dir
10.01 Ext1 start func enum 16 0…6 - In1
10.02 Ext1 start in1 Bit pointer 32 - - DI1
10.03 Ext1 start in2 Bit pointer 32 - - C.FALSE
10.04 Ext2 start func enum 16 0…6 - In1
10.05 Ext2 start in1 Bit pointer 32 - - DI1
10.06 Ext2 start in2 Bit pointer 32 - - C.FALSE
10.10 Fault reset sel Bit pointer 32 - - DI3
10.11 Run enable Bit pointer 32 - - C.TRUE
10.13 Em stop off3 Bit pointer 32 - - C.TRUE
10.15 Em stop off1 Bit pointer 32 - - C.TRUE
10.17 Start enable Bit pointer 32 - - C.TRUE
10.19 Start inhibit enum 16 0…1 - Disabled
10.20 Start intrl func enum 16 0…1 - Off3 stop
11 Start/stop mode
11.01 Start mode enum 16 0…2 - Automatic
11.02 Dc-magn time UINT32 16 0…10000 ms 500 ms
11.03 Stop mode enum 16 1…2 - Coast
11.04 Dc hold speed REAL 16 0…1000 rpm 5.0 rpm
11.05 Dc hold curr ref UINT32 16 0…100 % 30%
11.06 Dc hold enum 16 0…1 - Disabled
12 Operating mode
12.01 Ext1/Ext2 sel Bit pointer 32 - - DI5
12.05 Ext2 ctrl mode enum 16 1…2 - PID
13 Analogue inputs
13.01 AI1 filt time REAL 16 0…30 s 0.100 s
13.02 AI1 max REAL 16 -22…22 mA or -11…11 V mA or V 20.000 mA or
10.000 V
13.03 AI1 min REAL 16 -22…22 mA or -11…11 V mA or V 4.000 mA or
2.000 V
13.04 AI1 max scale REAL 32 -3276832768 - 1500.000
13.05 AI1 min scale REAL 32 -32768…32768 - 0.000
13.06 AI2 filt time REAL 16 0…30 s 0.100 s
13.07 AI2 max REAL 16 -22…22 mA or -11…11 V mA or V 20.000 mA or
10.000 V
13.08 AI2 min REAL 16 -22…22 mA or -11…11 V mA or V 4.000 mA or
2.000 V
13.09 AI2 max scale REAL 32 -3276832768 - 100.000
13.10 AI2 min scale REAL 32 -32768…32768 - 0.000
13.11 AI3 filt time REAL 16 0…30 s 0.100 s