EasyManua.ls Logo

ABB ACQ810 - Page 144

ABB ACQ810
376 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
144 Parameters
13.09 AI2 max scale Defines the real value that corresponds to the maximum
analog input AI2 value defined by parameter 13.07 AI2 max.
-32768.000 …
32768.000
Real value corresponding to maximum AI2 value. 1000 = 1
13.10 AI2 min scale Defines the real value that corresponds to the minimum
analog input AI2 value defined by parameter 13.08 AI2 min.
See the drawing at parameter 13.09 AI2 max scale.
-32768.000 …
32768.000
Real value corresponding to minimum AI2 value. 1000 = 1
13.11 AI3 filt time Defines the filter time constant for analog input AI3. See
parameter 13.01 AI1 filt time.
0.000 … 30.000 s Filter time constant. 1000 = 1 s
13.12 AI3 max Defines the maximum value for analog input AI3. The input
type depends on the type and/or settings of the I/O
extension module installed. See the user documentation of
the extension module.
-22.000 … 22.000
mA or
-11.000 11.000 V
AI3 maximum value. 1000 = 1 unit
13.13 AI3 min Defines the minimum value for analog input AI3. The input
type depends on the type and/or settings of the I/O
extension module installed. See the user documentation of
the extension module.
-22.000 … 22.000
mA or
-11.000 11.000 V
AI3 minimum value. 1000 = 1 unit
No. Name/Value Description FbEq
AI (scaled)
AI (mA/V)
13.09
13.07
13.08
13.10

Table of Contents

Other manuals for ABB ACQ810

Related product manuals