Parameters 145
13.14 AI3 max scale Defines the real value that corresponds to the maximum
analog input AI3 value defined by parameter 13.12 AI3 max.
-32768.000 …
32768.000
Real value corresponding to maximum AI3 value. 1000 = 1
13.15 AI3 min scale Defines the real value that corresponds to the minimum
analog input AI3 value defined by parameter 13.13 AI3 min.
See the drawing at parameter 13.14 AI3 max scale.
-32768.000 …
32768.000
Real value corresponding to minimum AI3 value. 1000 = 1
13.16 AI4 filt time Defines the filter time constant for analog input AI4. See
parameter 13.01 AI1 filt time.
0.000 … 30.000 s Filter time constant. 1000 = 1 s
13.17 AI4 max Defines the maximum value for analog input AI4. The input
type depends on the type and/or settings of the I/O
extension module installed. See the user documentation of
the extension module.
-22.000 … 22.000
mA or
-11.000 11.000 V
AI4 maximum value. 1000 = 1 unit
13.18 AI4 min Defines the minimum value for analog input AI4. The input
type depends on the type and/or settings of the I/O
extension module installed. See the user documentation of
the extension module.
-22.000 … 22.000
mA or
-11.000 11.000 V
AI4 minimum value. 1000 = 1 unit
No. Name/Value Description FbEq
AI (scaled)
AI (mA/V)
13.14
13.12
13.13
13.15