346 Control through the embedded fieldbus interface
Modbus register addresses for the ABB Drives classic profile
The table below shows the Modbus register addresses for the drive data with the
ABB Drives classic profile. This profile provides a converted 16-bit access to the drive
data.
Note: Only the least significant 16-bits of drive 32-bit control and status words can be
accessed.
Register Address Register Data (16-bit)
400001 Fieldbus control word (CW). See section Control word for the ABB
Drives profiles on page 339.
400002 Fieldbus reference 1 (REF1)
400003 Fieldbus reference 2 (REF2
400004 Fieldbus status word (SW). See section Status word for the ABB
Drives profiles on page 341.
400005 Fieldbus actual value 1 (ACT1)
400006 Fieldbus actual value 2 (ACT2)
400007 Fieldbus data in/out 1 (Drive parameter 58.35 Data I/O 1)
……
400030 Fieldbus data in/out 24 (Drive Parameter 58.58 Data I/O 24)
400101
409999 Register address (16-bit drive parameter) = 400000 + 100 × group +
index
Example: Modbus register address to drive parameter 03.18 is
400000 + 100 × 3 + 18 = 400318
Drive parameter access (32-bit drive parameter) = 420000 + 200
×
group + 2
× index
Example: Modbus register address to drive parameter 01.27
420000 + 200
× 1 + 2 × 27 = 420254