Parameters 237
0…65535 No. of messages with CRC errors. 1 = 1
58.21 Raw CW LSW Shows the LSW part of the Control Word which the drive
receives from the Modbus master. Read only.
0x0000…0xFFFF Bits 0…15 of the Control word as a hex value. 1 = 1
58.22 Raw CW MSW Shows the MSW part of the Control Word which the drive
receives from the Modbus master. Read only.
0x0000…0xFFFF Bits 16…32 of the Control word as a hex value. 1 = 1
58.23 Raw SW LSW Shows the LSW part of the Status Word which the drive
sends to the Modbus master. Read only.
0x0000…0xFFFF Bits 0…15 of the Status word as a hex value. 1 = 1
58.24 Raw SW MSW Shows the MSW part of the Status Word which the drive
sends to the Modbus master. Read only.
0x0000…0xFFFF Bits 16…32 of the Status word as a hex value. 1 = 1
58.25 Raw Ref 1 LSW Shows the LSW part of reference 1 which the drive receives
from the Modbus master. Read only.
0x0000…0xFFFF Bits 0…15 of reference 1 as a hex value. 1 = 1
58.26 Raw Ref 1 MSW Shows the MSW part of reference 1 which the drive receives
from the Modbus master. Read only.
0x0000…0xFFFF Bits 16…32 of reference 1 as a hex value. 1 = 1
58.27 Raw Ref 2 LSW Shows the LSW part of reference 2 which the drive receives
from the Modbus master. Read only.
0x0000…0xFFFF Bits 0…15 of reference 2 as a hex value. 1 = 1
58.28 Raw Ref 2 MSW Shows the MSW part of reference 2 which the drive receives
from the Modbus master. Read only.
0x0000…0xFFFF Bits 16…32 of reference 2 as a hex value. 1 = 1
58.30 Transmit delay Defines the delay time which the slave waits until it sends a
response.
0…65335 ms Transmit delay time. 1 = 1 ms
58.31 Ret app errors Selects whether the drive returns Modbus exception codes
or not.
No No 0
Yes Yes 1
58.32 Word order Defines the order of the data words in the Modbus frame.
MSW LSW Most significant word first, then Least significant word. 0
LSW MSW Least significant word first, then Most significant word. 1
58.35 Data I/O 1 Defines the address of the drive parameter which the
Modbus master accesses when it reads from or writes to the
register address corresponding to Modbus In/Out parameter
no. 1. The Modbus master defines the type of the data (input
or output).
The value is conveyed in a Modbus frame using two 16-bit
words. If the drive parameter is a 16-bit value, the LSW
(Least significant word) conveys the value. If the drive
parameter is a 32-bit value, the next Modbus In/Out
parameter is also reserved.
0…9999 Parameter address. Format: xxyy, where:
xx = parameter group
yy = parameter index
1 = 1