112 Parameters
Parameter listing
No. Name/Value Description FbEq
01
01 Actual values
Basic signals for monitoring of the drive.
01.01 Motor speed rpm Filtered, estimated motor speed in rpm. The filter time
constant can be adjusted using parameter 19.03
MotorSpeed filt.
100 = 1 rpm
01.02 Motor speed % Actual speed in percent of the motor synchronous speed. 100 = 1%
01.03 Output frequency Estimated drive output frequency in Hz. 100 = 1 Hz
01.04 Motor current Measured motor current in A. 100 = 1 A
01.05 Motor current % Motor current in percent of the nominal motor current. 10 = 1%
01.06 Motor torque Motor torque in percent of the nominal motor torque. See
also parameter 01.29 Torq nom scale.
10 = 1%
01.07 Dc-voltage Measured intermediate circuit voltage. 100 = 1 V
01.14 Motor speed est Estimated motor speed in rpm. 100 = 1 rpm
01.15 Temp inverter Estimated IGBT temperature in percent of fault limit. 10 = 1%
01.17 Motor temp1 Measured temperature of motor 1 in degrees Celsius when a
KTY sensor is used. (With a PTC sensor, the value is always
0.)
10 = 1 °C
01.18 Motor temp2 Measured temperature of motor 2 in degrees Celsius when a
KTY sensor is used. (With a PTC sensor, the value is always
0.)
10 = 1 °C
01.19 Used supply volt Either the user-given supply voltage (parameter 47.04
Supply voltage), or, if auto-identification is enabled by
parameter 47.03 SupplyVoltAutoId, the automatically
determined supply voltage.
10 = 1 V
01.21 Cpu usage Microprocessor load in percent. 1 = 1%
01.22 Power inu out Drive output power in kW or hp, depending on setting of
parameter 16.17 Power unit.
100 = 1 kW
or hp
01.23 Motor power Measured motor shaft power in kW or hp, depending on
setting of parameter 16.17 Power unit.
100 = 1 kW
or hp
01.24 kWh inverter Amount of energy that has passed through the drive (in
either direction) in kilowatt-hours. Can be reset by entering a
0 using the DriveStudio PC tool.
1 = 1 kWh
01.25 kWh supply Amount of energy that the drive has taken from the AC
supply in kilowatt-hours. Can be reset by entering a 0 using
the DriveStudio PC tool.
1 = 1 kWh
01.26 On-time counter On-time counter. The counter runs when the drive is
powered. Can be reset by entering a 0 using the DriveStudio
PC tool.
1 = 1 h
01.27 Run-time counter Motor run-time counter. The counter runs when the inverter
modulates. Can be reset by entering a 0 using the
DriveStudio PC tool.
Note: The drive logic uses this value for equalization of
pump running duties. See section Autochange (page 61).
1=1h
01.28 Fan on-time Running time of the drive cooling fan. Can be reset by
entering a 0 using the DriveStudio PC tool.
1 = 1 h
01.29 Torq nom scale Nominal torque which corresponds to 100%.
Note: This value is copied from parameter 99.12 Mot nom
torque if entered. Otherwise the value is calculated.
1000 =
1Nm