142 Parameters
Ext2 EXT2 is active. 1
DI1 The external control location is determined by the status of
digital input DI1 (as indicated by 02.01 DI status, bit 0).
1073742337
DI2 The external control location is determined by the status of
digital input DI2 (as indicated by 02.01 DI status, bit 1).
1073807873
DI3 The external control location is determined by the status of
digital input DI3 (as indicated by 02.01 DI status, bit 2).
1073873409
DI4 The external control location is determined by the status of
digital input DI4 (as indicated by 02.01 DI status, bit 3).
1073938945
DI5 The external control location is determined by the status of
digital input DI5 (as indicated by 02.01 DI status, bit 4).
1074004481
Const Bit pointer setting (see Terms and abbreviations on page
109).
-
Pointer
12.05 Ext2 ctrl mode Selects the operating mode for external control location
EXT2.
Speed Speed control. The reference is taken from the source
defined by parameter 21.02 Speed ref2 sel.
1
PID PID control. 2
13
13 Analogue inputs
Analog input signal processing.
13.01 AI1 filt time Defines the filter time constant for analog input AI1.
Note: The signal is also filtered due to the signal interface
hardware (approximately 0.25 ms time constant). This
cannot be changed by any parameter.
0.000 … 30.000 s Filter time constant. 1000 = 1 s
13.02 AI1 max Defines the maximum value for analog input AI1. The input
type is selected a jumper on the JCU Control Unit (see the
Hardware Manual of the drive).
-22.000 … 22.000
mA or
-11.000 11.000 V
Maximum AI1 value. 1000 = 1 unit
No. Name/Value Description FbEq
63
%
100
T
t
O = I × (1 - e
-t/T
)
I = filter input (step)
O = filter output
t = time
T = filter time constant
Unfiltered signal
Filtered signal