Parameters 191
DI5 Digital input DI5 (as indicated by 02.01 DI status, bit 4). 1074004481
Const Bit pointer setting (see Terms and abbreviations on page
109).
-
Pointer
27.35 PID bal ref Defines the PID balancing reference. The PID controller
output is set to this value when the source selected by
parameter 27.35 PID bal ref is 1.
-32768.0 …
32768.0%
PID balancing reference. 10 = 1%
27.36 Pump scal speed Defines pump speed that corresponds to 100% PID
controller output.
Speed scal 19.01 Speed scaling (see page 167). 1073746689
Pointer Value pointer setting (see Terms and abbreviations on page
109).
-
28
28 Procact sel
Process actual value (feedback) settings.
28.01 Act val 1/2 sel Selects the process actual value (1 or 2). Alternatively,
selects a source whose status determines which process
actual value is used (0 = Actual value 1; 1 = Actual value 2).
Note: This parameter is only effective when parameter 28.04
Act val func is set to Act1.
Act val 1 Process actual value 1 selected. 0
Act val 2 Process actual value 2 selected. 1
DI1 Status of digital input DI1 (as indicated by 02.01 DI status, bit
0) determines which process actual value is selected.
1073742337
DI2 Status of digital input DI2 (as indicated by 02.01 DI status, bit
1) determines which process actual value is selected.
1073807873
DI3 Status of digital input DI3 (as indicated by 02.01 DI status, bit
2) determines which process actual value is selected.
1073873409
DI4 Status of digital input DI4 (as indicated by 02.01 DI status, bit
3) determines which process actual value is selected.
1073938945
DI5 Status of digital input DI5 (as indicated by 02.01 DI status, bit
4) determines which process actual value is selected.
1074004481
Const Bit pointer setting (see Terms and abbreviations on page
109).
-
Pointer
28.02 Act val 1 src Selects the source of process actual value 1.
Zero No source selected. 0
AI1 scaled 02.05 AI1 scaled (see page 113). 1073742341
AI2 scaled 02.07 AI2 scaled (see page 113). 1073742343
AI3 scaled 02.09 AI3 scaled (see page 113). 1073742345
AI4 scaled 02.11 AI4 scaled (see page 114). 1073742347
AI5 scaled 02.13 AI5 scaled (see page 114). 1073742349
FBA procact 02.41 FBA act val (see page 122). 1073742377
Shared sig1 02.43
Shared signal 1 (see page 122). 1073742379
Flow act 05.05 Flow act (see page 125). 1073743109
Pointer Value pointer setting (see Terms and abbreviations on page
109).
-
No. Name/Value Description FbEq