190 Parameters
27.31 Pid out freeze Freezes, or defines a source that can be used to freeze, the
output of the process PID controller. This feature can be
used when, for example, a sensor providing process
feedback must be serviced without stopping the process.
The output of the PID controller is frozen as long as the
selected source is 1.
See also parameter 27.30 Pid ref freeze.
No Process PID controller output not frozen. 0
Freeze Process PID controller output frozen. 1
DI1 Activation of digital input DI1 (as indicated by 02.01 DI
status, bit 0) freezes process PID controller output.
1073742337
DI2 Activation of digital input DI2 (as indicated by 02.01 DI
status, bit 1) freezes process PID controller output.
1073807873
DI3 Activation of digital input DI3 (as indicated by 02.01 DI
status, bit 2) freezes process PID controller output.
1073873409
DI4 Activation of digital input DI4 (as indicated by 02.01 DI
status, bit 3) freezes process PID controller output.
1073938945
DI5 Activation of digital input DI5 (as indicated by 02.01 DI
status, bit 4) freezes process PID controller output.
1074004481
Const Bit pointer setting (see Terms and abbreviations on page
109).
-
Pointer
27.32 Pipefill ref acc Defines the time for the PID setpoint increase from 0 to
100%.
0 … 100 s PID setpoint acceleration time. 1 = 1 s
27.33 Pipefill ref dec Defines the time for the PID setpoint decrease from 100 to
0%.
0 … 100 s PID setpoint deceleration time. 1 = 1 s
27.34 PID bal ena Selects a source that enables the PID balancing reference
(see parameter 27.35 PID bal ref).
1 = PID balancing reference enabled.
DI1 Digital input DI1 (as indicated by 02.01 DI status, bit 0). 1073742337
DI2 Digital input DI2 (as indicated by 02.01 DI status, bit 1). 1073807873
DI3 Digital input DI3 (as indicated by 02.01 DI status, bit 2). 1073873409
DI4 Digital input DI4 (as indicated by 02.01 DI status, bit 3). 1073938945
No. Name/Value Description FbEq
04.05
27.12
27.01 PID
setpoint sel
27.13
27.14
27.15
27.16
27.18
27.19
PID
Process actual value
(group 28 Procact sel)