254 Parameters
77
77 Pump sleep
Sleep function settings.
See also section Sleep function on page 59.
77.01 Sleep mode sel Enables/disables the sleep function.
Not used Sleep function disabled. 0
Internal The signal selected by parameter 77.02 Sleep int sel is
compared to the value of 77.03 Sleep level. If the signal
remains below this value longer than the sleep delay (77.04
Sleep delay), the drive shifts to sleep mode.
The sleep and wake-up delays (77.04 Sleep delay and 77.11
Wake up delay) are in force.
1
External The sleep function is activated by the source selected by
parameter 77.05 Sleep ext sel.
The sleep delay (77.04 Sleep delay) is not in force but the
wake-up delay (77.11 Wake up delay) is.
2
Int+ext When the source selected by parameter 77.05 Sleep ext sel
is “1”, the sleep function works as with the setting Internal.
When the source selected by parameter 77.05 Sleep ext sel
is “0”, the sleep function is disabled.
3
Soft ext When the source selected by parameter 77.05 Sleep ext sel
is “0”, the sleep function is disabled.
When the source selected by parameter 77.05 Sleep ext sel
is “1”, the input of the PID controller is set to 0. After the drive
enters sleep mode, it will not wake up until the signal returns
to “0”.
4
77.02 Sleep int sel Selects the internal signal to be monitored by the sleep
function when parameter 77.01 Sleep mode sel is set to
Internal, Int+ext or Soft ext.
Speed 01.01 Motor speed rpm (see page 112). 1073742081
Speed % 01.02 Motor speed % (see page 112). 1073742082
AI1 02.04 AI1 (see page 113). 1073742340
AI1 scaled 02.05 AI1 scaled (see page 113 ). 1073742341
AI2 02.06 AI2 (see page 113). 1073742342
AI2 scaled 02.07 AI2 scaled (see page 113 ). 1073742343
Proc act 04.01 Act val (see page 123). 1073742849
Flow act 05.05 Flow act (see page 125). 1073743109
Pointer Value pointer setting (see Terms and abbreviations on page
109).
-
77.03 Sleep level Defines the start limit for the sleep function when parameter
77.01 Sleep mode sel is set to Internal, Int+ext or Soft ext.
-32768.00 …
32768.00
Sleep start level. 100 = 1
77.04 Sleep delay Defines the delay for the sleep start function. See parameter
77.03 Sleep level. When the monitored signal falls below the
sleep level, the counter starts. When the signal exceeds the
sleep level, the counter resets.
0 … 12600 s Sleep start delay. 1 = 1 s