172 Parameters
20.09 Maximum torque2 Defines the source of maximum torque limit 2 for the drive (in
percent of the motor nominal torque). See parameter 20.06
Torq lim sel.
AI1 scaled 02.05 AI1 scaled (see page 113 ). 1073742341
AI2 scaled 02.07 AI2 scaled (see page 113 ). 1073742343
FBA ref1 02.26 FBA main ref1 (see page 118). 1073742362
FBA ref2 02.27 FBA main ref2 (see page 118). 1073742363
Max torque1 20.07 Maximum torque1 (see page 171). 1073746951
Pointer Value pointer setting (see Terms and abbreviations on page
109).
-
20.10 Minimum torque2 Defines the source of minimum torque limit 2 for the drive (in
percent of the motor nominal torque). See parameter 20.06
Torq lim sel.
AI1 scaled 02.05 AI1 scaled (see page 113 ). 1073742341
AI2 scaled 02.07 AI2 scaled (see page 113 ). 1073742343
FBA ref1 02.26 FBA main ref1 (see page 118). 1073742362
FBA ref2 02.27 FBA main ref2 (see page 118). 1073742363
Neg max torq -20.09 Maximum torque2 (see page 172). 1073746949
Min torque1 20.08 Minimum torque1 (see page 171). 1073746952
Pointer Value pointer setting (see Terms and abbreviations on page
109).
-
20.12 P motoring lim Defines the maximum allowed power fed by the inverter to
the motor in percent of the motor nominal power.
0.0 … 1600.0% Maximum motoring power. 10 = 1%
20.13 P generating lim Defines the maximum allowed power fed by the motor to the
inverter in percent of the motor nominal power.
0.0 … 1600.0% Maximum generating power. 10 = 1%
21
21 Speed ref
Speed reference source selection and processing.
21.01 Speed ref1 sel Selects the source for speed reference 1.
Zero Zero speed reference. 0
AI1 scaled 02.05 AI1 scaled (see page 113 ). 1073742341
AI2 scaled 02.07 AI2 scaled (see page 113 ). 1073742343
Freq in 02.20 Freq in (see page 11 4 ). 1073742356
FBA ref1 02.26 FBA main ref1 (see page 118). 1073742362
FBA ref2 02.27 FBA main ref2 (see page 118). 1073742363
Panel 02.34 Panel ref (see page 118). 1073742370
EFB ref1 02.38 EFB main ref1 (see page 122). 1073742374
EFB ref2 02.39 EFB main ref2 (see page 122). 1073742375
Pointer Value pointer setting (see Terms and abbreviations on page
109).
-
21.02 Speed ref2 sel Selects the source for speed reference 2.
Note: The reference signal must be in the range 0…100.
Zero Zero speed reference. 0
AI1 scaled 02.05 AI1 scaled (see page 113 ). 1073742341
No. Name/Value Description FbEq

Table of Contents

Other manuals for ABB ACQ810

Related product manuals