Parameters 195
29.11 Reference step 6 Sets a percentage that is added to the process setpoint
when six auxiliary (direct-on-line) motors are running. See
parameter 29.06 Reference step 1.
0.00 … 100.00% Reference step 6. 100 = 1%
29.12 Reference step 7 Sets a percentage that is added to the process setpoint
when seven auxiliary (direct-on-line) motors are running.
See parameter 29.06 Reference step 1.
0.00 … 100.00% Reference step 7. 100 = 1%
30
30 Fault functions
Configuration of behavior of the drive upon various fault
situations.
30.01 External fault Selects a source for an external fault signal.
0 = External fault trip
1 = No external fault
DI1 Digital input DI1 (as indicated by 02.01 DI status, bit 0). 1073742337
DI2 Digital input DI2 (as indicated by 02.01 DI status, bit 1). 1073807873
DI3 Digital input DI3 (as indicated by 02.01 DI status, bit 2). 1073873409
DI4 Digital input DI4 (as indicated by 02.01 DI status, bit 3). 1073938945
DI5 Digital input DI5 (as indicated by 02.01 DI status, bit 4). 1074004481
Const Bit pointer setting (see Terms and abbreviations on page
109).
-
Pointer
30.02 Speed ref safe Defines the safe speed reference that is used with the Spd
ref Safe setting of supervision parameters 13.32 AI superv
func, 30.03 Local ctrl loss or 50.02 Comm loss func upon an
alarm. This speed is used when the parameter is set to Spd
ref Safe.
-30000 … 30000
rpm
Safe speed reference. 1 = 1 rpm
30.03 Local ctrl loss Selects how the drive reacts to a control panel or PC tool
communication break.
No No action taken. 0
Fault Drive trips on fault LOCAL CTRL LOSS (0x5300).1
Spd ref Safe The drive generates alarm LOCAL CTRL LOSS (0x5300)
and sets the speed to the speed defined by parameter 30.02
Speed ref safe.
WARNING! Make sure that it is safe to continue
operation in case of a communication break.
2
Last speed The drive generates alarm LOCAL CTRL LOSS (0x5300)
and freezes the speed to the level the drive was operating at.
The speed is determined by the average speed over the
previous 10 seconds.
WARNING! Make sure that it is safe to continue
operation in case of a communication break.
3
30.04 Mot phase loss Selects how the drive reacts when a motor phase loss is
detected.
No No action taken. 0
Fault The drive trips on fault MOTOR PHASE (0x3182).1
No. Name/Value Description FbEq