Fault tracing 315
2008 ID-RUN
(0xFF84)
08.05 Alarm word1 b8
Motor identification run is
on.
This alarm belongs to normal start-up
procedure. Wait until drive indicates that
motor identification is completed.
Motor identification is
required.
This alarm belongs to normal start-up
procedure.
Select how motor identification should be
performed, parameter 99.13 IDrun mode.
Start identification routines by pressing
Start key.
2009 EMERGENCY STOP
(0xF081)
08.05 Alarm word1 b9
Drive has received
emergency stop command
(OFF1/OFF3).
Check that it is safe to continue
operation.
Return emergency stop push button to
normal position (or adjust the fieldbus
Control Word accordingly).
Restart drive.
2013 DEVICE OVERTEMP
(0x4210)
08.05 Alarm word1 b13
Measured drive temperature
has exceeded internal alarm
limit.
Check ambient conditions.
Check air flow and fan operation.
Check heatsink fins for dust pick-up.
Check motor power against unit power.
2014 INTBOARD OVERTEMP
(0x7182)
08.05 Alarm word1 b14
Interface board (between
power unit and control unit)
temperature has exceeded
internal alarm limit.
Let drive cool down.
Check for excessive ambient
temperature.
Check for cooling fan failure.
Check for obstructions in the air flow.
Check the dimensioning and cooling of
the cabinet.
2017 FIELDBUS COMM
(0x7510)
08.06 Alarm word2 b1
Programmable alarm: 50.02
Comm loss func
Cyclical communication
between drive and fieldbus
adapter module or between
PLC and fieldbus adapter
module is lost.
Check status of fieldbus communication.
See appropriate User’s Manual of
fieldbus adapter module.
Check settings of parameter group 50
Fieldbus.
Check cable connections.
Check if communication master is able to
communicate.
2018 LOCAL CTRL LOSS
(0x5300)
08.06 Alarm word2 b2
Programmable alarm: 30.03
Local ctrl loss
Control panel or PC tool
selected as active control
location for drive has
ceased communicating.
Check PC tool or control panel
connection.
Check control panel connector.
Replace control panel in mounting
platform.
2019 AI SUPERVISION
(0x8110)
08.06 Alarm word2 b3
Programmable alarm: 13.32
AI superv func
An analog input has
reached limit defined by
parameter 13.33 AI superv
cw.
Check analog input source and
connections.
Check analog input minimum and
maximum limit settings.
2020 FB PAR CONF
(0x6320)
08.06 Alarm word2 b4
The drive does not have a
functionality requested by
PLC, or requested
functionality has not been
activated.
Check PLC programming.
Check settings of parameter group 50
Fieldbus.
2021 NO MOTOR DATA
(0x6381)
08.06 Alarm word2 b5
Parameters in group 99
have not been set.
Check that all the required parameters in
group 99 have been set.
Code
Alarm (fieldbus code),
other information
Cause What to do