238 Parameters
58.36 Data I/O 2 See parameter 58.35.
0…9999 See parameter 58.35.1 = 1
……
58.58 Data I/O 24 See parameter 58.35.
0…9999 See parameter 58.35.1 = 1
64
64 Load analyzer
Peak value and amplitude logger settings.
See also section Load analyzer on page 82.
64.01 PVL signal Selects the signal to be monitored by the peak value logger.
The signal is filtered using the filtering time specified by
parameter 64.02 PVL filt time.
The peak value is stored, along with other pre-selected
signals at the time, into parameters 64.0664.11.
Parameter 64.03 Reset loggers resets both the peak value
logger and amplitude logger 2. The latest time the loggers
were reset is stored into parameter 64.13.
Speed rpm 01.01 Motor speed rpm (see page 112). 1073742081
Speed % 01.02 Motor speed % (see page 112). 1073742082
Frequency 01.03 Output frequency (see page 112). 1073742083
Current 01.04 Motor current (see page 112). 1073742084
Current % 01.05 Motor current % (see page 112). 1073742085
Torqu e 01.06 Motor torque (see page 112 ). 1073742086
Dc-voltage 01.07 Dc-voltage (see page 112 ). 1073742087
Power inu 01.22 Power inu out (see page 112). 1073742102
Power motor 01.23 Motor power (see page 112). 1073742103
Process act 04.01 Act val (see page 123). 1073742849
Proc PID out 04.05 Process PID out (see page 123). 1073742853
Pointer Value pointer setting (see Terms and abbreviations on page
109).
-
64.02 PVL filt time Peak value logger filtering time. See parameter 64.01 PVL
signal.
0.00 … 120.00 s Peak value logger filtering time. 100 = 1 s
64.03 Reset loggers Selects the signal to reset the peak value logger and
amplitude logger 2. (Amplitude logger 1 cannot be reset.)
Const Bit pointer setting (see Terms and abbreviations on page
109).
-
Pointer
No. Name/Value Description FbEq