Parameters 239
64.04 AL signal Selects the signal to be monitored by amplitude logger 2.
The signal is sampled at 200 ms intervals when the drive is
running.
The results are displayed by parameters 64.24…64.33.
Each parameter represents an amplitude range, and shows
what portion of the samples fall within that range.
The signal value corresponding to 100% is defined by
parameter 64.05 AL signal base.
Parameter 64.03 Reset loggers resets both the peak value
logger and amplitude logger 2. The latest time the loggers
were reset is stored into parameter 64.13.
Note: Amplitude logger 1 is fixed to monitor motor current
(01.04 Motor current). The results are displayed by
parameters 64.14…64.23. 100% of the signal value
corresponds to the maximum output current of the drive (see
the appropriate Hardware Manual).
Speed rpm 01.01 Motor speed rpm (see page 112). 1073742081
Speed % 01.02 Motor speed % (see page 112 ). 1073742082
Frequency 01.03 Output frequency (see page 112). 1073742083
Current 01.04 Motor current (see page 112 ). 1073742084
Current % 01.05 Motor current % (see page 112 ). 1073742085
Torque 01.06 Motor torque (see page 112). 1073742086
Dc-voltage 01.07 Dc-voltage (see page 112). 1073742087
Power inu 01.22 Power inu out (see page 112). 1073742102
Power motor 01.23 Motor power (see page 11 2 ). 1073742103
Process act
04.01 Act val (see page 123). 1073742849
Proc PID out 04.05 Process PID out (see page 123). 1073742853
Pointer Value pointer setting (see Terms and abbreviations on page
109).
-
64.05 AL signal base Defines the signal value that corresponds to 100%
amplitude.
0.00 … 32768.00 Signal value corresponding to 100%. 100 = 1
64.06 PVL peak value1 Peak value recorded by the peak value logger.
-32768.00 …
32768.00
Peak value. 100 = 1
64.07 Date of peak The date on which the peak value was recorded.
01.01.80 … Peak occurrence date (dd.mm.yy). 1 = 1 d
64.08 Time of peak The time at which the peak value was recorded.
00:00:00 …
23:59:59
Peak occurrence time. 1 = 1 s
64.09 Current at peak Motor current at the moment the peak value was recorded.
-32768.00 …
32768.00 A
Motor current at peak. 100 = 1 A
64.10 Dc volt at peak Voltage in the intermediate DC circuit of the drive at the
moment the peak value was recorded.
0.00 … 2000.00 V DC voltage at peak. 100 = 1 V
No. Name/Value Description FbEq