Parameters 221
Moderate Flux level is limited during the braking. Deceleration time is
longer compared to full braking.
1
Full Maximum braking power. Almost all available current is used
to convert the mechanical braking energy to thermal energy
in the motor.
2
44
44 Maintenance
Maintenance counter configuration.
See also section Maintenance counters on page 82.
44.01 Ontime1 func Configures on-time counter 1. This counter runs whenever
the signal selected by parameter 44.02 Ontime1 src is on.
After the limit set by parameter 44.03 Ontime1 limit is
reached, an alarm specified by parameter 44.04 Ontime1
alm sel is given, and the counter reset.
The current value of the counter is readable from parameter
04.09 Counter ontime1. Bit 0 of 06.15 Counter status
indicates that the count has exceeded the limit.
44.02 Ontime1 src Selects the signal to be monitored by on-time counter 1. See
parameter 44.01 Ontime1 func.
RO1 Relay output RO1 (as indicated by 02.02 RO status, bit 0). 1073742338
Running Bit 3 of 06.01 Status word1 (see page 126). 1073939969
Charged Bit 9 of 06.02 Status word2 (see page 127). 1074333186
Const Bit pointer setting (see Terms and abbreviations on page
109).
-
Pointer
44.03 Ontime1 limit Sets the alarm limit for on-time counter 1. See parameter
44.01 Ontime1 func.
0…2147483647 s Alarm limit for on-time counter 1.
44.04 Ontime1 alm sel Selects the alarm for on-time counter 1. See parameter
44.01 Ontime1 func.
On-time1 Pre-selectable alarm for on-time counter 1. 0
Device clean Pre-selectable alarm for on-time counter 1. 1
Add cool fan Pre-selectable alarm for on-time counter 1. 2
Cabinet fan Pre-selectable alarm for on-time counter 1. 3
Dc-capacitor Pre-selectable alarm for on-time counter 1. 4
Mot bearing Pre-selectable alarm for on-time counter 1. 5
No. Name/Value Description FbEq
Bit Function
0
Counter mode
0 = Loop: If alarm is enabled by bit 1, the alarm stays active only for 10 seconds.
1 = Saturate: If alarm is enabled by bit 1, the alarm stays active until reset.
1
Alarm ena (Alarm enable)
0 = Disable: No alarm is given when limit is reached.
1 = Enable: Alarm is given when limit is reached.