Parameters 127
06.02 Status word2 Status word 2 of the drive. -
No. Name/Value Description FbEq
Bit Name Information
0 Start act 1 = Drive start command is active.
0 = Drive start command is inactive.
1 Stop act 1 = Drive stop command is active.
0 = Drive stop command is inactive.
2 Ready relay 1 = Ready to function: run enable signal on, no fault, emergency stop signal
off, no ID run inhibition. Connected by default to DIO1 by par. 14.03 DIO1
out src.
0 = Not ready to function.
3 Modulating 1 = Modulating: IGBTs are controlled, ie. the drive is RUNNING.
0 = No modulation: IGBTs are not controlled.
4 Ref running 1 = Normal operation is enabled. Running. Drive follows the given
reference.
0 = Normal operation is disabled. Drive is not following the given reference
(eg. in magnetization phase drive is modulating).
5 Reserved
6 Off1 1 = Emergency stop OFF1 is active.
0 = Emergency stop OFF1 is inactive.
7 Start inh
mask
1 = Maskable (by par. 12.01 Start inhibit) start inhibit is active.
0 = No maskable start inhibit is active.
8 Start inh
nomask
1 = Non-maskable start inhibit is active.
0 = No non-maskable start inhibit is active.
9 Chrg rel
closed
1 = Charging relay is closed.
0 = Charging relay is open.
10 Sto act 1 = Safe torque off function is active. See parameter 30.07 Sto diagnostic.
0 = Safe torque off function is inactive.
11 Sleep
active
1 = Sleep mode active.
0 = Sleep mode inactive.
12 Ramp in 0 1 = Ramp Function Generator input is forced to zero.
0 = Normal operation.
13 Ramp hold 1 = Ramp Function Generator output is held.
0 = Normal operation.
14 Ramp out 0 1 = Ramp Function Generator output is forced to zero.
0 = Normal operation.
15 Reserved

Table of Contents