146 Parameters
13.19 AI4 max scale Defines the real value that corresponds to the maximum
analog input AI4 value defined by parameter 13.17 AI4 max.
-32768.000 …
32768.000
Real value corresponding to maximum AI4 value. 1000 = 1
13.20 AI4 min scale Defines the real value that corresponds to the minimum
analog input AI4 value defined by parameter 13.18 AI4 min.
See the drawing at parameter 13.19 AI4 max scale.
-32768.000 …
32768.000
Real value corresponding to minimum AI4 value. 1000 = 1
13.21 AI5 filt time Defines the filter time constant for analog input AI5. See
parameter 13.01 AI1 filt time.
0.000 … 30.000 s Filter time constant. 1000 = 1 s
13.22 AI5 max Defines the maximum value for analog input AI5. The input
type depends on the type and/or settings of the I/O
extension module installed. See the user documentation of
the extension module.
-22.000 … 22.000
mA or
-11.000 … 11.000 V
AI5 maximum value. 1000 = 1 unit
13.23 AI5 min Defines the minimum value for analog input AI5. The input
type depends on the type and/or settings of the I/O
extension module installed. See the user documentation of
the extension module.
-22.000 … 22.000
mA or
-11.000 … 11.000 V
AI5 minimum value. 1000 = 1 unit
No. Name/Value Description FbEq
AI (scaled)
AI (mA/V)
13.19
13.17
13.18
13.20