162 Parameters
15.12 AO2 src min Defines the real value of the signal (selected by parameter
15.07 AO2 src) that corresponds to the minimum AO2 output
value (defined by parameter 15.10 AO2 out min). See
parameter 15.11 AO2 src max.
-32768.000 …
32768.000
Real signal value corresponding to minimum AO2 output
value.
1000 = 1
15.13 AO3 src Selects a drive signal to be connected to analog output AO3.
Speed rpm 01.01 Motor speed rpm (see page 112). 1073742081
Speed % 01.02 Motor speed % (see page 112). 1073742082
Frequency 01.03 Output frequency (see page 112). 1073742083
Current 01.04 Motor current (see page 112). 1073742084
Current % 01.05 Motor current % (see page 112). 1073742085
Torqu e 01.06 Motor torque (see page 112 ). 1073742086
Dc-voltage 01.07 Dc-voltage (see page 112 ). 1073742087
Power inu 01.22 Power inu out (see page 112). 1073742102
Power motor 01.23 Motor power (see page 112). 1073742103
SpRef unramp 03.03 SpeedRef unramp (see page 123). 1073742595
SpRef ramped 03.05 SpeedRef ramped (see page 123). 1073742597
SpRef used 03.06
SpeedRef used (see page 123). 1073742598
TorqR ef us ed 03.14 Torq ref used (see page 123). 1073742606
Proc PID out 04.05 Process PID out (see page 123). 1073742853
Process act% 04.22 Act val % (see page 124). 1073742870
Pointer Value pointer setting (see Terms and abbreviations on page
109).
-
15.14 AO3 filt time Defines the filtering time constant for analog output AO3.
See parameter 15.02 AO1 filt time.
0.000 … 30.000 s Filter time constant. 1000 = 1 s
15.15 AO3 out max Defines the maximum output value for analog output AO3.
0.000 … 22.700 mA Maximum AO3 output value. 1000 = 1 mA
15.16 AO3 out min Defines the minimum output value for analog output AO3.
0.000 … 22.700 mA Minimum AO3 output value. 1000 = 1 mA
No. Name/Value Description FbEq