130 Parameters
06.20 Pump status word Pump status word. -
06.21 Level status Level control status word. -
No. Name/Value Description FbEq
Bit Name Value Information
0 Trad 1 Traditional pump control mode active.
1 Reg bypass 1 PID controller bypass mode active.
2 Multi pump 1 Multipump functionality (via drive-to-drive link) active.
3 Level control 1 Level control active.
4 Sleep 1 Sleep mode active.
5 Boosting 1 Sleep boost active.
6 Pipe filling 1 Soft pipefill function active.
7Bypass 1TBA
8 Cleaning 1 Cleaning sequence active.
9 Analyzer ID run 1 Reserved
10 PID ref freeze 1 PID controller input frozen.
11 PID out freeze 1 PID controller output frozen.
12 Balancing 1 PID balancing reference in force.
13 No aux pumps 1 No auxiliary pumps available to be started.
14 Autochange 1 Autochange function active.
15 High prot spd 1 Outlet pressure monitoring: forced reference active.
16 Low prot spd 1 Inlet pressure monitoring: forced reference active.
17 Speed ref 2 act 1 Speed reference 2 active.
18 Ext2 Speed
mode
1 Speed control selected for external control location EXT2 by
parameter 12.05 Ext2 ctrl mode.
19…31 Reserved
Bit Name Value Information
0 Low level 1 1 Low level 1 reached.
1 Low level 2 1 Low level 2 reached.
2 Stop level 1 Stop level reached.
3 Start level 1 1 Start level 1 reached.
4 Start level 2 1 Start level 2 reached.
5 Start level 3 1 Start level 3 reached.
6 Start level 4 1 Start level 4 reached.
7 Start level 5 1 Start level 5 reached.
8 Start level 6 1 Start level 6 reached.
9 Start level 7 1 Start level 7 reached.
10 Start level 8 1 Start level 8 reached.
11 High level 1 1 High level 1 reached.
12 High level 2 1 High level 2 reached.
13 High speed 1 High speed reached.
14…31 Reserved